40
Operation by the start command from
the operation panel (PU operation mode)
3.5.5
Perform frequency setting by analog (current input)
[Connection diagram]
POINT
· Use
/
to give a start command.
· Turn the AU signal on.
·
Pr. 79 Operation mode selection
must be set to "4" (external/PU combined operation mode 2)
Three-phase
AC power supply
Motor
5(-)
4(+)
AU
Inverter
R/L1
S/L2
T/L3
U
V
W
AU signal
FR-DU07
,
Output of the
adjustment meter
(4 to 20mADC)
SD
CAUTION
When both the forward switch and reverse
switch turn on, the inverter will not start.
Also, if both switch turn on while running,
the inverter stops.
Flickering
( )
The parameter number
read previously appears.
Display
Operation
8.
Start
Check that the terminal 4 input selection signal
(AU) is on.
Press the start switch (or ).
FWD or REV of operation status indication flickers.
7.
Mode/monitor check
Press twice to choose the monitor/frequency
monitor.
1.
Screen at powering on
The monitor display appears.
2.
Press to choose the parameter setting mode.
3.
Turn until (
Pr. 79
) appears.
4.
Press to read the currently set value.
" "(initial value) appears.
5.
Turn clockwise to change it to the setting
value of " ".
6.
Press to set.
Flicker ··· Parameter setting complete!!