Features
Options
Precautions
Motor
Connection
example
Standard
specs.
Outline
dimensions
Parameter
list
Parameter
descriptions
Protective
functions
IPM motor
control
Compatibility
W
a
rranty
Te
rminal connection
diagrams
T
e
rminal specs.
Operation panel
Parameter unit
FR Configurator
27
Freq
uency
detection
41
Up-to-frequency sensitivity
0 to 100%
0.1%
10%
42
Output frequency detection
0 to 400Hz
0.01Hz
6Hz
43
Output frequency detection for reverse
rotation
0 to 400Hz, 9999
0.01Hz
9999
Second
funct
ions
44
Second acceleration/deceleration time
0 to 3600s
0.1s
5/15s
45
Second deceleration time
0 to 3600s, 9999
0.1s
9999
46
Second torque boost
0 to 30%, 9999
0.1%
9999
47
Second V/F (base frequency)
0 to 400Hz, 9999
0.01Hz
9999
48
Second stall prevention operation
current
0 to 150%, 9999
0.1%
9999
51
Second electronic thermal O/L relay
0 to 500A, 9999
0.01A
9999
Monitor functions
52
DU/PU main display data selection
0, 5, 8 to 12, 14, 20,
23 to 25, 50 to 55, 61,
62, 64, 100
1
0
54
FM terminal function selection
1 to 3, 5, 8 to 12, 14, 21,
24, 50, 52, 53, 61, 62
1
1
55
Frequency monitoring reference
0 to 400Hz
0.01Hz
60Hz
56
Current monitoring reference
0 to 500A
0.01A
Rated
inverter
current
Aut
omati
c
rest
art
fu
ncti
on
s
57
Restart coasting time
0, 0.1 to 5s, 9999
0.1s
9999
58
Restart cushion time
0 to 60s
0.1s
1s
—
59
Remote function selection
0 to 3
1
0
—
60
Energy saving control selection
0, 9
1
0
—
65
Retry selection
0 to 5
1
0
—
66
Stall prevention operation reduction
starting frequency
0 to 400Hz
0.01Hz
60Hz
Retr
y
67
Number of retries at fault occurrence
0 to 10, 101 to 110
1
0
68
Retry waiting time
0.1 to 600s
0.1s
1s
69
Retry count display erase
0
1
0
—
70
Special regenerative brake duty
0 to 30%
0.1%
0%
—
71
Applied motor
0, 1, 3, 13, 23, 40, 43,
50, 53, 120, 210
1
0
—
72
PWM frequency selection
0 to 15
1
1
—
73
Analog input selection
0, 1, 10, 11
1
1
—
74
Input filter time constant
0 to 8
1
1
—
75
Reset selection/disconnected PU
detection/PU stop selection
0 to 3, 14 to 17
1
14
—
77
Parameter write selection
0 to 2
1
0
—
78
Reverse rotation prevention selection
0 to 2
1
0
—
79
Operation mode selection
0 to 4, 6, 7
1
0
Motor const
ant
s
80
Motor capacity
0.4 to 15kW, 9999
0.01kW
9999
82
Motor excitation current
0 to 500A, 9999
0.01A
9999
83
Rated motor voltage
0 to 1000V
0.1V
200V/400V
84
Rated motor frequency
10 to 120Hz
0.01Hz
60Hz
90
Motor constant (R1)
0 to 50
, 9999
0.001
9999
96
Auto tuning setting/status
0, 11, 21
1
0
PU
conne
ctor
co
mmunication
117
PU communication station number
0 to 31 (0 to 247)
1
0
118
PU communication speed
48, 96, 192, 384
1
192
119
PU communication stop bit length
0, 1, 10, 11
1
1
120
PU communication parity check
0 to 2
1
2
121
Number of PU communication retries
0 to 10, 9999
1
1
122
PU communication check time interval
0, 0.1 to 999.8s, 9999
0.1s
0s
123
PU communication waiting time setting
0 to 150ms, 9999
1ms
9999
124
PU communication CR/LF selection
0 to 2
1
1
—
125
Terminal 2 frequency setting gain
frequency
0 to 400Hz
0.01Hz
60Hz
—
126
Terminal 4 frequency setting gain
frequency
0 to 400Hz
0.01Hz
60Hz
Func-
tion
Parameter
Name
Setting Range
Minimum
Setting
Increments
Initial
Value
Refer
to
Page
Customer
Setting
Summary of Contents for F720PJ-11KF