When setting parameters, refer to the instruction manual (applied) and understand instructions.
You can select the reset input acceptance, disconnected PU (FR-
PU07) connector detection function and PU stop function.
Reset selection
You can select the operation timing of reset function (RES signal,
reset command through communication) input.
Disconnected PU detection
This function detects that the PU (FR-PU07) has been disconnected
from the inverter for longer than 1s and causes the inverter to
provide an alarm output (E.PUE) and come to an alarm stop.
PU stop selection
In any of the PU operation, External operation and network
operation modes, the motor can be stopped by pressing
of
the PU.
You can select whether write to various parameters can be
performed or not. Use this function to prevent parameter values
from being rewritten by misoperation.
This function can prevent reverse rotation fault resulting from the
incorrect input of the start signal.
Used to select the operation mode of the inverter.
Mode can be changed as desired among operation using external
command signals (External operation), operation from the operation
panel and PU (FR-PU07) (PU operation), combined operation of PU
operation and External operation (External/PU combined operation),
and Network operation (when RS-485 communication is used).
75
Reset selection, disconnected PU
detection
Pr.75 Reset selection/disconnected PU detection/PU stop selection
Pr.75
setting Reset Selection
Disconnected
PU Detection
PU Stop
Selection
0
Reset input normally
enabled.
If the PU is
disconnected,
operation will be
continued as-is.
Pressing
decelerates the
motor to a stop only
in the PU operation
mode.
1
Reset input enabled
only when the
protective function is
activated.
2
Reset input normally
enabled.
When the PU is
disconnected, the
inverter output is
shut off.
3
Reset input enabled
only when the
protective function is
activated.
14
(initial
value)
Reset input normally
enabled.
If the PU is
disconnected,
operation will be
continued as-is.
Pressing
decelerates the
motor to a stop in
any of the PU,
external and
communication
operation modes.
15
Reset input enabled
only when the
protective function is
activated.
16
Reset input normally
enabled.
When the PU is
disconnected, the
inverter output is
shut off.
17
Reset input enabled
only when the
protective function is
activated.
77
Prevention of parameter rewrite
Pr.77 Parameter write selection
Pr.77
setting
Description
0 (initial value)
Write is enabled only during a stop.
1
Parameter write is not enabled.
2
Parameter write is enabled in any operation mode
regardless of operation status.
78
Prevention of reverse rotation of the
motor
Pr.78 Reverse rotation prevention selection
Pr.78
setting
Description
0 (initial value)
Both forward and reverse rotations allowed
1
Reverse rotation disabled
2
Forward rotation disallowed
79, 340
Operation mode selection
Pr.79 Operation mode selection
Pr.340 Communication startup mode selection
Pr.79
setting
Description
LED Indication
:Off
:On
0
(initial
value)
External/PU switchover mode ( Press
to switch between the PU and External
operation mode.)
External operation mode at power-on
PU operation
mode
External operation
mode
NET operation
mode
1
Fixed to PU operation mode
PU operation
mode
2
Fixed to external operation mode
Operation can be performed by switching
between the External and Net operation
mode.
External operation
mode
NET operation
mode
3
External/PU combined operation mode 1
External/PU
combined
operation mode
Running frequency
Start signal
Operation panel and PU
(FR-PU07) setting or
external signal input
(multispeed setting,
across terminals 4 and
5 (valid when AU signal
turns ON)).
External signal
input (terminal
STF, STR)
4
External/PU combined operation mode 2
Running frequency
Start signal
External signal
input (terminal 2, 4,
Jog, multi-speed
setting, etc)
Input from the
operation panel
and PU (FR-
PU07)
(
)
6
Switch-over mode
Switch among PU operation, External
operation, and NET operation while
keeping the same operation status.
PU operation
mode
External operation
mode
NET operation
mode
7
External operation mode (PU operation
interlock)
X12 signal ON
Operation mode can be switched to the
PU operation mode. (output stop during
External operation)
X12 signal OFF
Operation mode cannot be switched to
the PU operation mode.