When setting parameters, refer to the instruction manual (applied) and understand instructions.
If an alarm occurs, the inverter resets itself automatically to restart.
You can also select the alarm description for a retry.
When selection of automatic restart after instantaneous power
failure is selected (
Pr. 57 Restart coasting time
9999), restart
operation is performed at retry operation as at an instantaneous
power failure.
Use
Pr. 65
to select the alarm to be activated for retries.
"
" indicates the alarms selected for retry.
Set the number of retries at alarm occurrence in
Pr. 67
.
Use
Pr. 68
to set the waiting time from when an inverter alarm occurs
until a retry is made in the range 0.1 to 600s.
Reading the
Pr. 69
value provides the cumulative number of
successful restart times made by retry. (This can be cleared by
setting "0".)
Setting of the used motor selects the thermal characteristic
appropriate for the motor.
Setting is required when using a constant-torque motor or IPM
motor. Thermal characteristic of the electronic thermal relay
function suitable for the motor is set.
For the 5.5K and 7.5K, the
Pr. 0 Torque boost
and
Pr. 12
DC injection
brake operation voltage
settings are automatically changed according
to the
Pr. 71
setting as follows.
Pr.71
setting: 0, 3, 23, 40, 43, 120, 210
Pr.71
setting: 1, 13, 50, 53
65, 67 to 69
Retry function at alarm occurrence
Pr.65 Retry selection
Pr.67 Number of retries at fault occurrence
Pr.68 Retry waiting time
Pr.69 Retry count display erase
Alarm
Indication for
Retry
Pr.65
Setting
0
1
2
3
4
5
E.OC1
E.OC2
E.OC3
E.OV1
E.OV2
E.OV3
E.THM
E.THT
E.UVT
E. BE
E. GF
E.OHT
E.PTC
E.OLT
E. PE
E.ILF
E.CDO
E.PID
E.OS
E.SOT
This function is available only under IPM motor control.
Pr.67
Setting
Description
0 (initial value)
No retry function
1 to 10
Set the number of retries at alarm
occurrence. An alarm output is not provided
during retry operation.
101 to 110
Set the number of retries at alarm
occurrence. (The setting value of minus 100
is the number of retries.)
An alarm output is provided during retry
operation.
66
Refer to the section about
Pr.22
67 to 69
Refer to the section about
Pr.65
70
Refer to the section about
Pr.30
71, 450
Use the constant torque motor
(applied motor)
Pr.71 Applied motor
Pr.450 Second applied motor
Pr.71, Pr.450
setting
Used motor
Thermal Characteristic
of the Electronic
Thermal Relay Function
Pr.71 Pr.450
Standard Constant
torque
IPM
0
Standard motor (such as SF-JR)
1
Mitsubishi constant-torque motor
(such as SF-JRCA)
40
Mitsubishi high-efficiency motor
(SF-HR)
50
Mitsubishi constant-torque motor
(SF-HRCA)
3
Standard motor
Select
"offline
auto
tuning
setting"
13
Constant-torque motor
23
Mitsubishi standard
motor
(SF-JR 4P 1.5kW or less)
43
Mitsubishi high-efficiency
motor (SF-HR)
53
Mitsubishi constant-
torque motor (SF-HRCA)
120
High-efficiency IPM motor (MM-EF)
210
High-efficiency IPM motor (MM-EFS)
9999
Without second applied motor (
Pr.450
initial value)
Automatic
Change
Parameter
Standard Motor
Setting
Constant-
torque Motor
Setting
Pr. 0
3%
2%
Pr. 12
4%
2%
V/F
V/F
V/F
GP
MFVC
GP
MFVC
GP
MFVC