ThermiStar L .. SP 01/03/10
7. Operation startup
59
Pump control
-
Circulating pump control
-
Unscrew pump stopper and turn pump shaft as illustrated below.
-
Screw pump stopper back in
-
Caution: Collect drops
Fig. 34:
Remove pump stopper
Switching on the device
Once the proper installation verification and testing has been com-
pleted, the power can be switched on. In order to do so, activate the
installed power switch and automatic fuse.
Refrigerant dosage
The amount of refrigerant is established through the measurement
and comparison of the refrigerant condensation temperature and
heating pump flow temperature. The heat pump / compressor must
be activated for min. of 10 min. and a flow temperature of approx.
50°C must be reached, before measurement or the results will not
be reliable and the amount of refrigerant indicated will not be cor-
rect. The difference between these two temperatures should be be-
tween 0 and 3 K (condensation temperature - flow temperature).
Test for leak-tightness
Once operating, the refrigerant circuit must be rechecked for leak-
age using a sensitive leak detection device/mittel.
Summary of Contents for 98.30000-6324
Page 1: ...ThermiStar L SP 01 03 10 ...
Page 18: ...5 Technical Data ThermiStar L SP 01 03 10 18 5 2 Type plate Fig 4 Sample type plate ...
Page 21: ...ThermiStar L SP 01 03 10 5 Technical Data 21 ...
Page 39: ...ThermiStar L SP 01 03 10 6 Assembly 39 Fig 11 Sensor cable heat source intake 5 ...
Page 68: ...8 Maintenance ThermiStar L SP 01 03 10 68 8 4 Spare part drawing and legend Fig 40 ...
Page 88: ...Your notes ThermiStar L SP 01 03 10 88 ...
Page 89: ...ThermiStar L SP 01 03 10 Your notes 89 ...
Page 90: ...Your notes ThermiStar L SP 01 03 10 90 ...
Page 92: ......