8. Maintenance
ThermiStar L .. SP 01/03/10
64
8.3
Work activities to be
performed
CAUTION!
Risk of injury due to refrigerant!
Refrigerant is corrosive and causes cold burns upon
contact with skin.
Therefore:
-
Wear chemical-resistant protective gloves when
handling refrigerant at any time.
-
Wear protective glasses to avoid contact with eyes
NOTE!
For operators of equipment containing 3kg or more
of refrigerant the following duties of documentation
apply:
-
Amount and type of refrigerant
-
Any amounts of refrigerant refills
-
Any amounts of refrigerant retrieved during startup,
maintenance or final disposal
-
Details identifying the company or technical per-
sonnel that carried out the installation, startup, or
any maintenance work
-
Dates and results of all inspections
The recorded information must be presented to the
relevant authorities and the commission upon re-
quest.
CAUTION!
Risk of injury due to refrigerant!
Refrigerant leakage damages the environment 100-
24,000 times more than carbon dioxide (CO2).
Therefore:
-
Hermetically sealed systems that contain 6 kg of
refrigerant or more must not exceed a leakage rate
of 1%.
-
Hermetically sealed systems that contain 6 kg of
refrigerant or more must have leak-tightness
inspected and verified at least every 12 months.
-
All leaks from which refrigerant can escape must be
repaired immediately.
Summary of Contents for 98.30000-6324
Page 1: ...ThermiStar L SP 01 03 10 ...
Page 18: ...5 Technical Data ThermiStar L SP 01 03 10 18 5 2 Type plate Fig 4 Sample type plate ...
Page 21: ...ThermiStar L SP 01 03 10 5 Technical Data 21 ...
Page 39: ...ThermiStar L SP 01 03 10 6 Assembly 39 Fig 11 Sensor cable heat source intake 5 ...
Page 68: ...8 Maintenance ThermiStar L SP 01 03 10 68 8 4 Spare part drawing and legend Fig 40 ...
Page 88: ...Your notes ThermiStar L SP 01 03 10 88 ...
Page 89: ...ThermiStar L SP 01 03 10 Your notes 89 ...
Page 90: ...Your notes ThermiStar L SP 01 03 10 90 ...
Page 92: ......