ThermiStar L .. SP 01/03/10
6. Assembly
55
LED in-
dications
Status
OFF
Flashing
ON
Green
Power OFF
Not available
Power ON
Yellow
Idle / Setup
Ramping*
Bypass ON
Red
Not available
Internal overheat
alarm*
Motor overheat
alarm
Phase sequence
alarm*
Phase loss alarm
Overload alarm*
Phase imbalance
alarm
Yellow
Manual
Not available
Auto
Class 10 Protec-
tion
Class 20 Protec-
tion
Phase sequence
alarm disabled
Phase sequence
alarm enabled
* Will flash simultaneously in case of fault
Push button:
Default MANUELL (Hold Button: RESET)
Default 10 (Hold Button: TEST)
ENABLE or DISABLE: Default ENABLE
Current settings
ThermiStar L 10 8,2 A
ThermiStar L 13 10,1 A
ThermiStar L 15 11,8 A
ThermiStar L 19 16,0 A
Multiplier/Current Limit
Multiplier/Current limit (Knob 3)
Ramp-up time multiplier by either 0.5, 1.0, 1.5, 2.0
(default x1)
Either 150%, 250% 350%, 450%