ThermiStar L .. SP 01/03/10
5. Technical Data
27
Legend for Fig. 7:
Abbr.
Meaning
Abbr.
Meaning
- When using fault current circuit breakers,
observe separate neutral leads for normal
and special tariff!
- Observe identical phase potential of the
control circuits for normal and special tariff!
- The individual relay outputs of the heating
controller withstand a max. load of 4 A (at
cos Phi>0.6).
- Max. total current for terminals: 6 A.
- This must be considered when choosing the
circulating pumps. Use contactors if
necessary.
KMT
Refrigerant temperature liquid
KP Condensor
pump
LG Performance
limit
M1 Condenser
motor
MV-A
Solenoid refrigerant circulation thawing
(normally closed)
MV-FLL
Solenoid refrigerant circulation liquid
gas line (normally closed)
MV-Hz
Solenoid refrigerant circulation heating
(normally closed)
N / N1
Neutral lead
A1
Relay coil L
ND
Pressure switch low pressure
A2
Relay coil N
NOT
Control switch for emergency switch
(if needed)
AF Outside
sensor
AVS 37 Control unit
(NTf)
Normal tariff
EW-S
Mains supply lock
PKZM
Motor protection switch
F1
Fine-wire fuse condenser pump / Ventilator
split evaporator 4 AT
QAA 75 Room device
QE
Source intake (sensor)
F2
Fine-wire fuse controller RVS 61.843 4 AT
RL-WP Return heat pump (sensor)
HD
Pressure switch high pressure
RVS 61 Heat pump controller
HS Main
switch
S1 Motor control unit
INT
Winding protection INT
(STf)
Special tariff
K2
Relay toggle heating/thawing
V-SP
Ventilator split evaporator
K3
Relay condensor pump
VDT
Flow temperature
K4
Relay ventilator split evaporator
VER
Condensor
VL-WP Flow - heat pump
NOTE!
Terminal assignment of the heat pump controller RVS 61 see pages 28-29
Summary of Contents for 98.30000-6324
Page 1: ...ThermiStar L SP 01 03 10 ...
Page 18: ...5 Technical Data ThermiStar L SP 01 03 10 18 5 2 Type plate Fig 4 Sample type plate ...
Page 21: ...ThermiStar L SP 01 03 10 5 Technical Data 21 ...
Page 39: ...ThermiStar L SP 01 03 10 6 Assembly 39 Fig 11 Sensor cable heat source intake 5 ...
Page 68: ...8 Maintenance ThermiStar L SP 01 03 10 68 8 4 Spare part drawing and legend Fig 40 ...
Page 88: ...Your notes ThermiStar L SP 01 03 10 88 ...
Page 89: ...ThermiStar L SP 01 03 10 Your notes 89 ...
Page 90: ...Your notes ThermiStar L SP 01 03 10 90 ...