ThermiStar L .. SP 01/03/10
6. Assembly
43
Connection of split evaporator with
heat pump
CAUTION!
Risk of injury due to refrigerant!
Refrigerant is corrosive and causes cold burns upon
contact with skin.
Therefore:
-
Wear chemical-resistant protective gloves when
handling refrigerant at any time.
-
Wear protective glasses to avoid contact with eyes.
-
Connect the heat pump and the split evaporator with the
refrigerant lines.
CAUTION!
Environmental damage due to improper assembly of
the refrigerant line!
Refrigerant and compressor oil can leak!
Therefore:
-
Only use tools recommended for work on cooling
devices: Bending pliers, pipe cutters, countersink
and bordering tools
-
Take note of bending radius to avoid bending or
breaking of pipes.
-
To avoid brittle or cracking pipes, do not bend the
pipes repeatedly.
-
In order to reduce loss of pressure and to ensure
return of compressor oil, avoid unnecessary
bending of the pipes.
-
Use appropriate fastening and insulation during
refrigerant line installation.
-
Use only non-cutting tools (special pipe cutting
tools) to shorten refrigerant lines.
NOTE!
The heating pump contains refrigerant for a 20 m
max. length cooling line.
Any shortening or lengthening of the line may only
be carried out by a certified technician. The refriger-
ant dosage must then be checked accordingly.
NOTE!
The technician must check the installation and
mountings of the pipe, and establish a proper con-
nection with the heating pump and the split evapora-
tor.
NOTE!
Ball valves must remain shut (delivery condition)!
Summary of Contents for 98.30000-6324
Page 1: ...ThermiStar L SP 01 03 10 ...
Page 18: ...5 Technical Data ThermiStar L SP 01 03 10 18 5 2 Type plate Fig 4 Sample type plate ...
Page 21: ...ThermiStar L SP 01 03 10 5 Technical Data 21 ...
Page 39: ...ThermiStar L SP 01 03 10 6 Assembly 39 Fig 11 Sensor cable heat source intake 5 ...
Page 68: ...8 Maintenance ThermiStar L SP 01 03 10 68 8 4 Spare part drawing and legend Fig 40 ...
Page 88: ...Your notes ThermiStar L SP 01 03 10 88 ...
Page 89: ...ThermiStar L SP 01 03 10 Your notes 89 ...
Page 90: ...Your notes ThermiStar L SP 01 03 10 90 ...
Page 92: ......