7. Operation startup
ThermiStar L .. SP 01/03/10
58
7.3 Startup
NOTE!
The customer / owner of the system must be present
when starting up the system.
A startup protocol must be established on site.
NOTE!
For operators of equipment containing 3 kg or more
of refrigerant the following duties of documentation
apply:
-
Amount and type of refrigerant
-
Any amounts of refrigerant refills
-
Any amounts of refrigerant retrieved during startup,
maintenance or final disposal
-
Details identifying the company or technical per-
sonnel that carried out the installation, startup, or
any maintenance work
-
Dates and results of all inspections
The recorded information must be presented to the
relevant authorities and the commission upon re-
quest.
CAUTION!
Risk of injury due to refrigerant!
Refrigerant leakage damages the environment 100-
24,000 times more than carbon dioxide (CO
2
).
Therefore:
-
Hermetically sealed systems that contain 6 kg of re-
frigerant or more must not exceed a leakage rate of
1%.
CAUTION!
Device damage through wrong direction of rotation of
the condenser!
Reverse running for several hours or day causes
serious damages with loss of warranty.
Therefore:
-
The use of the condenser requires that the correct
direction of rotation is determined and observed
(right rotating field).
-
When turning in the wrong direction, the condenser
works much louder than usual and does not
produce any output (compressed gas neck remains
cold). A brief reverse run of a few minutes is not
harmful.
Refer also to the "Startup order form".
Summary of Contents for 98.30000-6324
Page 1: ...ThermiStar L SP 01 03 10 ...
Page 18: ...5 Technical Data ThermiStar L SP 01 03 10 18 5 2 Type plate Fig 4 Sample type plate ...
Page 21: ...ThermiStar L SP 01 03 10 5 Technical Data 21 ...
Page 39: ...ThermiStar L SP 01 03 10 6 Assembly 39 Fig 11 Sensor cable heat source intake 5 ...
Page 68: ...8 Maintenance ThermiStar L SP 01 03 10 68 8 4 Spare part drawing and legend Fig 40 ...
Page 88: ...Your notes ThermiStar L SP 01 03 10 88 ...
Page 89: ...ThermiStar L SP 01 03 10 Your notes 89 ...
Page 90: ...Your notes ThermiStar L SP 01 03 10 90 ...
Page 92: ......