27
5
Num
Flag
Object
Function
Length
DPT
Function
Description
41
42
43
45
44
[A:ECG 1]
Lock
[A:ECG 1]
Auto Off
[A:ECG 1]
Operation
Hours Rese
[A:ECG 1]
Operation
Hours
Exeeded
[A:ECG 1]
Operation
Hours
Value
(in seconds)
[A:ECG 1]
Operation
Hours
Value
(in seconds)
Enable
(DPT1.003)
Enable
(DPT1.003)
Reset
(DPT1.015)
Alarm
(DPT1.005)
Time lag(s)
(DPT13.100)
Time lag(h)
(DPT7.007)
1 bit
1 bit
1 bit
1 bit
4 bytes
2 bytes
CW
CW
CW
CRT
CRT
0 = Unlock;
1 = Lock
0 = Disable;
1= Enable
1 = Reset
0 = No
Exeeded;
1 = Exeeded
4-Bytes
Value in
Second
2-Bytes
Value
in Hours
This object is used
to lock/unlock the
ECG.
This object is used
to enable/disable
the Auto Off function
of the ECG.
Resets the
operating hours
counter of the ECG.
This object is used
to report that the
operation hours'
counter exceeds the
set threshold.
The operating hours
of the ECG in
seconds are sent
via this object. The
internal counter can
be set to 0 (Reset)
or another value via
this object.
The operating hours
of the ECG in hours
are sent via this
object. The internal
counter can be set
to 0 (Reset) or
another value via
this object.
28
5
Num
Flag
Object
Function
Length
DPT
Function
Description
46
47
[A:ECG 1]
Failure
(Status)
[A:ECG 1]
Converter
Test Control
Alarm
(DPT1.005)
Converter test
control
(DPT20.611)
1 bit
1 byte
CRT
CW
0 = No Error;
1 =Error
Control
Test
Command
Reports the
presence of an ECG
disconnect.
This object is used
to controls a test of
a DALI converter
Furthermore, it
allows to stop
running test and to
reset test flags.
These object
follows the following
coding:
Bit 0: Reserved.
Bit 1: Start function
test.
Bit 2: Start duration
test.
Bit 3: Start partial
duration test.
Bit 4: Stop test.
Bit 5: Reset function
test done flag.
Bit 6: Reset duration
test done flag .
Bit 7 – 255:
Reserved.