51
6
6 2 1
. . .1 ECG (out group) - NAME&TYPE
The chart shows the dynamic range for this parameter:
ETS-text
ECG Name
ECG Type
Value in emergency
mode
★
●
Fluorescent
Lamp
Self Contained
●
Battery Lamp
Discharge Lamp
●
Low Voltage
●
Halogen Lamp
Incandescent
●
Lamp
0..10V Converter
●
●
LED Module
●
Relay Module
LED Module
-----
0 – 100%
[50%]
Dynamic range
[
]
default value
[
]
default value
Comment
You can enter a user-
friendly name in the ECG.
There are 30 bytes allowed
for name setting.
Use this parameter to set
the type of ECG used.
Sets the brightness level of
the lamp in emergency
mode.
52
6
ETS-text
Prolong time on
recovery
★
Function test
interval
★
Duration test
interval
★
Test execution
time
★
★
Self Contained Battery Lamp
in
ECG
: Only appears when “
”
“
” is
Type
chosen
0 - 255days
[2days]
0 – 20 min
[0min]
0 – 52 weeks
[2weeks]
0 - 255days
[7days]
Dynamic range
[
]
default value
[
]
default value
Comment
Sets the time to remain in
the extended emergency
mode after main voltage
recovery.
Sets the periodic time for
automatic execution of the
test which checks the
proper function of the
converter.
Sets the periodic time for
automatic execution of the
test which checks
converter is working
properly in case of power
failure.
Sets the maximum time
after which the function
test or duration test must
be executed. If a test has
not ended within this time
the result will indicate max
delay exceeded.