The following chart shows the objects that belong to general

setting:

Number

933

934

4 bit

1 byte

[A:Group1]

Relative

Dimming

[A:Group1]

Absolute

Dimming

Name

Length

Usage

This object is used for

the relative dimming of

the group.

This object is used for

the absolute dimming of

the group.

Sends status signals from

the object On/Off(Status)

with the option you

selected.

Sends status signals from
the objects On/Off(Status)
at intervals you desire.

Sends status signals from
the object Dimming
Value(Status) with the
option you selected.

Sends status signals from
the objects Dimming
Value(Status) at intervals
you desire.

Send On/Off

status

Send status cyclic

(0=no active)

Send dimming
value status

Send status cyclic

(0=no active)

no send, passive

status object

at change

always at input

of telegram

at change

0 65535s

[0s]

no send, passive

status object

at change

always at input

of telegram

at change

0 65535s

[0s]

Dynamic range

[

]

default value

[

]

default value

The chart shows the dynamic range for this parameter:

6 3 5

. . Group STATUS

ETS-text

Comment

78

6

The following chart shows the objects that belong to general

setting:

Number

935

936

1 bit

1 byte

[A:Group1]

On/Off(Status)

[A:Group1]

Dimming Value

(Status)

Name

Length

Usage

This object is used to

send the switch status of

the group.

1.The parameter: Send

On/Off Status is no

send, passive stage

object  update status

but no send telegram

2.The parameter: Send

On/Off Status is at

change  send telegram

in every on/off change

3.The parameter: Send

On/Off Status is always

at input of telegram

send telegram in every

on/off command

Send Status cyclic is at a

certain time value  send

telegram at regular

intervals.

Sends the dimming value
of the group.
1.The parameter: Send

dimming value status
is no send, passive
stage object  update
value status but no
send telegram.

2.The parameter: Send

dimming value status is
at change  send
telegram in every
dimming value change.

Summary of Contents for DLC-02-KN

Page 1: ...A DA DA DALI B Prog 1s RJ 45 ETHERNET KN KN KNX DLC 02 KN DALI Gateway MEAN WELL ENTERPRISES CO LTD No 28 Wuquan 3rd Rd Wugu Dist New Taipei City 24891 Taiwan Manual www meanwell com manual html Made...

Page 2: ...KNX installation Room based lighting control is conveniently incorporated into the higher level KNX system building management system The device transforms switch and dim commands from the connected K...

Page 3: ...cal pecification 6 S 3 Installation 3 1 Concept of Commissioning 3 ounting 2 M 3 3 Electrical Configuration 3 iring 4 W 3 5 ETS App DCA 3 6 Parameter Configuration 4 DALI Commissioning 5 Communication...

Page 4: ...facturer MEANWELL Enterprise Co Ltd Product family Lighting Product type Gateway Product name DLC 02 KN Order number DLC 02 KN l Two independent DALI Bus channels with built in DALI power supply up to...

Page 5: ...ctions for the relay output K2 Connections for the relay output K3 Connections for the relay output K4 Display Move button for the display Set button for the display Exit button for the display Progra...

Page 6: ...or devices to the relays Connect the gateway to KNX bus ALL devices with mains connected Load ETS database and install DAC app ETS DCA DALI commissioning and group assignment Configure ETS parameters...

Page 7: ...ion of 1 5 The maximum length is 300m with a cable mm KNX end l The maximum number of bus devices connected is 256 l The maximum length of a line segment is 350 m measured along the line between the p...

Page 8: ...gateway is based on the standard surface for the configuration of communication objects and parameters as well as a special surface for configuring the DALI bus system This special surface is designe...

Page 9: ...LI Commissioning Following the physical installation and wiring of the DALI ECGs and lights and the electronic commissioning the connected ECGs need to be learnt in To do so please open the commission...

Page 10: ...nds can control the ECG 2 4 14 Hit2 There are 16 scenes available to be used Check a scene to activate it Hit3 Further DALI parameters such as Power ON level System Failure level Maximum Minimum level...

Page 11: ...Num 1 2 3 4 Dali A Broadcast Switch Dali A Broadcast Absolute Dimming Dali A Scene Control Dali A Activate Panic mode Switch DPT 1 001 Percentage DPT 5 001 Scene control DPT 18 001 Start Stop DPT 1 01...

Page 12: ...connected DALI segment Reports the presence of a DALI short circuit in the connected DALI segment 18 5 Num 9 10 11 Dali A ECG Presence Dali A ECG Diagnostics Dali A On Off Status Group 1 Gruop16 Alar...

Page 13: ...to ECG 33 to ECG 48 Sends the on off status for ECG 46 64 Bit 0 15 refer to ECG 49 to ECG 64 DALI Bus B broadcast switch This object is used to switch all connected lights simultaneously on or off 19...

Page 14: ...nt 22 5 Num Flag Object Function Length DPT Function Description 25 26 27 Dali B ECG Diagnostics Dali B On Off Status Group 1 Gruop16 Dali B On Off Status ECG1 ECG 16 Diagnostics value DPT 238 600 Bit...

Page 15: ...at regular intervals when active This object is use to switch all relays on off Note This object is only valid when the parameter All Relays On Off is checked Sends the on off status for the relays 1...

Page 16: ...nd Status cyclic is at a certain time value send telegram at regular intervals 26 5 Num Flag Object Function Length DPT Function Description 40 A ECG 1 Dimming Value Status percentage DPT5 001 1 byte...

Page 17: ...s the set threshold The operating hours of the ECG in seconds are sent via this object The internal counter can be set to 0 Reset or another value via this object The operating hours of the ECG in hou...

Page 18: ...mode active Bit 6 Extended emergency mode active Bit 7 FT in progress Bit 8 DT in progress Bit 9 PDT in progress Bit 10 15 Reserved 30 5 Num Flag Object Function Length DPT Function Description LTRF S...

Page 19: ...33 934 935 A Group1 On Off A Group1 Relative Dimming A Group1 Absolute Dimming A Group1 On Off Stat us Switch DPT1 001 4 bit Dimming control DPT 3 007 Percentage DPT5 001 Switch DPT1 001 1 bit 4 bit 1...

Page 20: ...oup1 Operation Hours Reset Enable DPT1 003 Enable DPT1 003 Time lag s DPT13 100 Time h DPT7 007 Reset DPT1 015 1 bit 1 bit 4 bytes 2 bytes 1 bit CW CW CRT CW 0 Unlock 1 Lock 0 Disable 1 Enable 4 Bytes...

Page 21: ...ject is used to lock unlock the relay This object is used to send the status of the relay This object is used to send the inverted status of the relay Note This object is only valid when the parameter...

Page 22: ...s triggered This object only available when the object Addition object is set at percentage Activate or deactivates the Effect Note This object is only valid when the parameter Effect function is chec...

Page 23: ...Send operation cyclic 0 not active 2 60s 2s Central Function Operation 0 65535mins 0mins Dynamic range default value Name Length Comment Usage All functions run after startup timeout finished NOTE Th...

Page 24: ...n KNX bus is on return Actions are all off all on no action all set to a certain value or all stay at last value Use this parameter to set a desired value This option only exists when defined value in...

Page 25: ...1 General setting RELAY CONTROL The chart shows the dynamic range for this parameter ETS text Relay n control n 1 4 All Relays On Off Output mode Send status Send status cyclic 0 not active Checked i...

Page 26: ...verted status Behavior at locking Behavior at unlocking normally opened normally closed normally opened 0 65535s 0s 0 65535s 0s Unchecked Checked no send passive status object at change always at inpu...

Page 27: ...inverted status of the relay Note This object is only valid when the parameter Additional inverted state is checked Forced control function 00 and 01 Deactivates Forced control 10 Sets to Forced cont...

Page 28: ...installation no use There is no ECG found or connected out group The ECG has been found and NOT assigned to a group in group The ECG has been found and assigned to a group 6 2 ECGs enable 50 6 6 2 1 E...

Page 29: ...rolong time on recovery Function test interval Duration test interval Test execution time Self Contained Battery Lamp in ECG Only appears when is Type chosen 0 255days 2days 0 20 min 0min 0 52 weeks 2...

Page 30: ...done flag Bit 7 255 Reserved 54 6 Number Name Length Usage 48 1 bit A ECG 1 Converter Status Converter Mode This object is used to send the status of a converter with the following coding Bit 0 Unkno...

Page 31: ...icates the method by which the last test started Updated when a test is finish Bit 0 Unknown Bit 1 Started automatically LTRF SF LDTR LPDTR SD SP LTRD LTRP 0 N N U U U U U U U U U U U U U U U U U U U...

Page 32: ...6 2 1 3 ECG out group DIMMING CURVE ETS text Comment 58 6 Sets the dimming curve for the ECG Dimming curve log linear log Dynamic range default value default value The chart shows the dynamic range fo...

Page 33: ...this parameter ETS text Comment 6 The following chart shows the objects that belong to general setting Number 37 38 4 bit 1 byte A ECG 1 Relative Dimming A ECG 1 Absolute Dimming Name Length Usage Th...

Page 34: ...Status cyclic is at a certain time value send telegram at regular intervals 62 6 Number 40 46 1 byte 1 bit A ECG 1 Dimming Value Status A ECG 1 Failure Status Name Length Usage Sends the dimming value...

Page 35: ...ocking 0 unlock 1 lock 0 lock 1 unlock 0 unlock 1 lock Switch off value Switch on value no action defined value no action Dynamic range default value default value The chart shows the dynamic range fo...

Page 36: ...arameter ETS text Comment 66 6 Use this parameter to activate the mode Determines whether an individual operating hour calculation is required for the ECG Use this parameter to select the value for th...

Page 37: ...is object is used to report that the operation hours counter exceeds the set threshold The operating hours of the ECG in seconds are sent via this object The internal counter can be set to 0 Reset or...

Page 38: ...ault value default value The chart shows the dynamic range for this parameter ETS text Comment 70 6 Dynamic range default value default value ETS text Comment Sets the periodic time for automatic exec...

Page 39: ...ds are sent via this object The internal counter can be set to 0 Reset or another value via this object The operating hours of the ECG in hours are sent via this object The internal counter can be set...

Page 40: ...ange for this parameter ETS text ETS text Comment Comment 74 6 Use this parameter to set a desired value This option only exists when defined value in Value on DALI Power Fail is chosen Sets the dimmi...

Page 41: ...his parameter 6 3 3 Group SWITCH ETS text Comment 76 6 The following chart shows the objects that belong to general setting Number 932 1 bit A Group1 On Off Name Length Usage This object is used to sw...

Page 42: ...change always at input of telegram at change 0 65535s 0s Dynamic range default value default value The chart shows the dynamic range for this parameter 6 3 5 Group STATUS ETS text Comment 78 6 The fo...

Page 43: ...ws the dynamic range for this parameter ETS text Comment 80 6 Use this parameter to set a desired value This option only exists when defined value in Behavior at locking is chosen Sets the action to b...

Page 44: ...o set the value of all lamps in a group in mode Night Time count before setting to the dimming value in the group after the mode is triggered Night mode Value Delay time Night mode checked Only appear...

Page 45: ...rt shows the dynamic range for this parameter ETS text Comment The following chart shows the objects that belong to general setting Number 939 1 bit A Group1 Operation Hours Reset Name Length Usage Re...

Page 46: ...rameter to activate the function Select which ECG to work with This option only exists when Dali X ECG in Control type is chosen X A or B Set a desired time to trigger the timer Set a desired time to...

Page 47: ...on object Switch value Percentage value Timer dimming checked Only appears when is Unchecked Checked Unchecked Unchecked Checked Unchecked Unchecked Checked Unchecked Unchecked Checked Unchecked Unche...

Page 48: ...im value 64 effect steps can be programmed by an effect function An effect step can also be programmed as a delay 90 6 Choose which segment group or ECG to work with this effect Choose which ECG or gr...

Page 49: ...not replace parts or any form of modification to the product in order to keep the warranty effectively MEAN WELL possesses the right to adjust the content of this manual Pleaserefertothelatest versio...

Page 50: ...No 28 Wuquan 3rd Rd Wugu Dist New Taipei City 248 Taiwan...

Reviews: