The following chart shows the objects that belong to general
setting:
Number
47
1 byte
[A:ECG 1]
Converter Test
Control
Name
Length
Usage
This object is used to
controls a test of a DALI
converter. Furthermore,
it allows to stop running
test and to reset test
flags. These object
follows the following
coding:
Bit 0: Reserved.
Bit 1: Start function test.
Bit 2: Start duration test.
Bit 3: Start partial
duration test.
Bit 4: Stop test.
Bit 5: Reset function test
done flag.
Bit 6: Reset duration
test done flag
Bit 7 – 255: Reserved.
54
6
Number
Name
Length
Usage
48
1 bit
[A:ECG 1]
Converter
Status
Converter Mode. This
object is used to send
the status of a converter
with the following
coding:
Bit 0: Unknown.
Bit 1: Normal mode
active.
Bit 2: Inhibit mode
active: for 15
minutes the
converter will not
switch the
emergency
lighting on when a
power failure
occurring.
Bit 3: Hardwired inhibit
mode active:
digital input that
the converter can
have to activate
the inhibit mode.
Bit 4: Rest mode active:
forced off
emergency
lighting during
emergency mode.
Bit 5: Emergency mode
active.
Bit 6: Extended
emergency mode
active.
Bit 7: FT in progress.
Bit 8: DT in progress.
Bit 9: PDT in progress.
Bit 10 - 15: Reserved.