Num
12
13
14
15
16
[Dali A]
On/Off
(Status
ECG1-ECG
16)
[Dali A]
On/Off
(Status
ECG17-ECG
32)
[Dali A]
On/Off
(Status
ECG33-ECG
48)
[Dali A]
On/Off
(Status
ECG49-ECG
64)
[Dali B]
Broadcast
Switch
Bit-combined
info on/off
(DPT 27.001)
Bit-combined
info on/off
(DPT 27.001)
Bit-combined
info on/off
(DPT 27.001)
Bit-combined
info on/off
(DPT 27.001)
Switch
(DPT1.001)
4 bytes
4 bytes
4 bytes
4 bytes
1 bit
CRT
CRT
CRT
CRT
CW
Status
ECG 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
Bit 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
ECG 3 on: 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
Status
Status
Status
On/Off
Flag
Object
Function
Length
DPT
Function
Description
Sends the on/off
status for ECG 1 -
16. Bit 0 -15 refer to
ECG 1 to ECG 16.
For example:
Sends the on/off
status for ECG 17 -
32. Bit 0 -15 refer to
ECG 17 to ECG 32.
Sends the on/off
status for ECG 33 -
48. Bit 0 -15 refer to
ECG 33 to ECG 48.
Sends the on/off
status for ECG 46 –
64. Bit 0 -15 refer to
ECG 49 to ECG 64.
DALI Bus B
broadcast switch.
This object is used
to switch all
connected lights
simultaneously on
or off.
19
5
20
5
Num
17
18
19
20
[Dali B]
Broadcast
Absolute
Dimming
[Dali B]
Scene
Control
[Dali B]
Activate
Panic
Mode
Dali B]
Activate
Night Mode
Percentage
(DPT5.001)
Scene
control
(DPT18.001)
Start/Stop
(DPT1.010)
Start/Stop
(DPT1.010)
1 byte
1 byte
1 bit
1 bit
CW
CW
CW
CW
Absolute
Dimming
Scene No
Activate/Stop
Activate/Stop
Flag
Object
Function
Length
DPT
Function
Description
DALI Bus B
broadcast absolute
dimming.
This object is used
to simultaneously
set all connected
lights to a certain
value.
DALI Bus A - scene
controlling.
DALI Bus B - Panic
mode.
Activates or
deactivates the
panic mode via the
bus.
Note: This object is
only valid when the
parameter “Panic
mode” is checked.
DALI Bus B - Night
mode.
Activates or
deactivates the
night mode via the
bus.
Note: This object is
only valid when the
parameter “Night
mode” is checked.