47
6
ETS-text
Priority/
Force control
Behavior after
KNX Bus power up
off
●
on
●
●
no change
●
no change
●
2Bit forced control
1Bit priority ON
●
1Bit priority OFF
●
no change
Dynamic range
[
]
default value
[
]
default value
Comment
Activates or deactivates
the function.
Uses this parameter to set
the behaviors of the relay
when KNX bus is on/ return.
The following chart shows the objects that belong to general
setting:
Number
2180
2181
2182
2183
2184
1 bit
1 bit
1 bit
1 bit
2 bit
[Relay 1] On/Off
[Relay 1] Lock
[Relay 1]On/Off
(Status)
[Relay 1]
On/Off
(Inverted Status)
[Relay 1]
Forced Control
Name
Length
Usage
This object is used to
switch the relay on or off.
This object is used to
lock/unlock the relay.
This object is used to
send the status of the
relay.
This object is used to
send the inverted status
of the relay.
Note: This object is only
valid when the
parameter “Additional
inverted state” is
checked.
Forced control function:
00 and 01: Deactivates
Forced control
10: Sets to Forced control
active with relay Off
(open)
11: Sets to Forced control
active with relay On
(short)
48
6
6
6
.1.1. General setting - RTC
The chart shows the dynamic range for this parameter:
ETS-text
RTC Send status
cyclic
not active, 10s,
20s, …50s, 60s
[not active]
Dynamic range
[
]
default value
[
]
default value
Comment
Sends status signals from
the objects “RTC Time”
and “RTC date” at
intervals you desire.
The following chart shows the objects that belong to general
setting:
Number
34
35
3 bytes
3 bytes
[Central Function]
RTC
[Central Function]
RTC
Name
Length
Usage
This object is used to
set the time. The time
must be provided by a
central timer and
updated at least twice a
day.
This object is used to
set the date. The date
must be provided by a
central timer and
updated at least twice a
day.