33
5
Num
Flag
Object
Function
Length
DPT
Function
Description
936
[A:Group1]
Dimming
Value
(Status)
Percentage
(DPT5.001)
1 byte
CRT
0 - 100%
Sends the dimming
value of the group.
1.The parameter:
Send dimming
value status is no
send, passive
stage object
update value
status but no send
telegram.
2.The parameter:
Send dimming
value status is at
change send
telegram in every
dimming value
change.
3.The parameter:
Send dimming
value status is
always at input of
telegram send
telegram in every
dimming
command.
4.Send Status cyclic
is at a certain time
value send
telegram at
regular intervals.
34
5
Num
Flag
Object
Function
Length
DPT
Function
Description
937
938
940
939
[A:Group1]
Lock
[A:Group1]
Auto Off
[A:Group1]
Operation
Hours Value
[A:Group1]
Operation
Hours
Reset
Enable
(DPT1.003)
Enable
(DPT1.003)
Time lag(s)
(DPT13.100)
Time (h)
(DPT7.007)
Reset
(DPT1.015)
1 bit
1 bit
4 bytes
2 bytes
1 bit
CW
CW
CRT
CW
0 = Unlock;
1 = Lock
0 = Disable;
1 = Enable
4-Bytes
Value in
Second
2-Bytes
Value in
Hours
1 = Reset
0 =Lock;
1 = Unlock
0 = Enable;
1 = Disable
This object is used
to lock/unlock the
group.
This object is used
to enable/disable
the Auto Off function
of the group.
This object only
appears when the
parameter “Auto-off
disable/enable
object” chose “0 =
enable;1 = disable”.
The operating hours
of the group in
seconds are sent
via this object. The
internal counter can
be set to 0 (Reset)
or another value via
this object.
The operating hours
of the group in hours
are sent via this
object. The internal
counter can be set
to 0 (Reset) or
another value via
this object.
Resets the
operating hours
counter of the group.
This object only
appears when the
parameter “Lock
object polarity”
chose “0 = lock; 1 =