55
6
Number
Name
Length
Usage
49
6 bytes
[A:ECG 1]
Converter
Test Result
This object is used to
send the result of the
last converter test with
the following coding:
LTRF, LTRD, LTRP:
Last
Test Result Functional /
Duration / Partial
duration: Indicates the
test result of each type:
Bit 0: Unknown.
Bit 1: Passed in time.
Bit 2: Passed max delay
exceeded.
Bit 3: Failed, test
executed in time.
Bit 4: Failed, max delay
exceeded.
Bit 5: Test manually
stopped.
Bit 6 - 15: Reserved.
SF, SD, SP:
Start method
of last Functional /
Duration / Partial test
.
Indicates the method
by which the last test
started. Updated when
a test is finish.
Bit 0: Unknown.
Bit 1: Started
automatically.
LTRF
SF
LDTR
LPDTR
SD SP
LTRD LTRP 0
N
N
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U
U U U U U U U U
N
N
N
r r r
r
r
r
N
N
N
N
N
N
N
N
N
N
N
N
N
0 0
0
0
0
56
6
Number
Name
Length
Usage
Bit 2: Started by
Gateway.
Bit 3: Reserved.
LDTR
: Last Duration
Test Result. Contains
the battery discharge
time as the result of the
last successful duration
test indicated in
minutes.
LPDTR:
Last Partial
Duration Test Result.
Provides the remaining
battery charge level
after the last partial
duration test.
0: Deep discharge point.
Bit 1 - 253: Battery level.
Bit 254: Fully charged.
Bit 255: Unknown.
6.2.1.2 ECG (out group) - FAILURE&RECOVERY