15
Please remember that at this point all operations that have been
performed are only displayed in the work space. They are not
immediately loaded onto the DALI gateway. To start the process o
f
downloading the settings onto the gateway and the ECGs, you must
press the “Download” button.
Once the download is complete, all previously planned ECGs are
programmed in the system with the DALI configuration.
Attention
: Please be aware that the download on the “commissioning
page” only programs the DALI configuration data onto the
gateway and ECGs. The actual ETS application with
parameter settings and group addresses still has to be
downloaded onto the device. This is done, as usual, via the
normal download process in the ETS.
4
4
16
5.Communication Objects
5
5.1 Summary and Usage
Num
1
2
3
4
[Dali A]
Broadcast
Switch
[Dali A]
Broadcast
Absolute
Dimming
[Dali A]
Scene
Control
[Dali A]
Activate
Panic mode
Switch
(DPT 1.001)
Percentage
(DPT 5.001)
Scene
control
(DPT 18.001)
Start/Stop
(DPT 1.010)
1 bit
1 byte
1 byte
1bit
CW
CW
CW
CW
On/Off
Absolute
Dimming
Scene No.
Activate/Stop
Flag
Object
Function
Length
DPT
Function
Description
DALI Bus A -
broadcast switch.
This object is used
to switch all
connected lights
simultaneously on
or off.
DALI Bus A -
broadcast absolute
dimming.
This object is used
to simultaneously
set all connected
lights to a certain
value.
DALI Bus A - scene
controlling.
This object can be
used for calling
scenes.
DALI Bus A - Panic
mode.
Activates or
deactivates the
panic mode via the
bus.
Note: This object is
only valid when the
parameter “Panic
mode” is checked.
Communication objects available for communication of the device via
the KNX are shown in the table below. The objects are, in parts,
displayed or hidden, depending on how the parameters are set.