KJM MANDÍK
–
Detailed operating instructions
M&C KJMPNO 07/2022
MANDÍK, a.s.,
74
1.
SupplyState
= Set.
2.
Polarity
= Invert.
Assignment of digital outputs
13.3
Assigning digital outputs is done in the
Assignm.DigitalOutput
menu where the line of the
required digital output is assigned to the required component to be controlled by this output (e.g.
for a supply fan switched from output Q1 to
DO.Q1 = FS)
. A list of the component abbreviations
used in the digital output assignments is shown in Table 2. The assignment also includes the
option to invert the output state (
Normal
/Invert)
. Another option is to assign a constant value
(
Off
/
On
)
to the selected output by setting the output to
Set.
Example of setting the output Q1
permanently On:
DO.Q1 = Set, Invert.
The component abbreviations in the table are also given for
the previous SW version 28.01.
Device component name
Abbreviation
v28.01
Abbreviation
v29.01
Supply fan – switch on
FanS
FS
Exhaust fan – switch on
FanE
FE
Mixing damper - open
DmpM
DM
Recuperator – switch on
Rec
Rc
Water heating 2 – switch on
5
WH2
Glycol refill pump - on
AGl
AG
Water heating 1 – switch on
WtH
WH
Water heating 1 – switch on
ElH
EH
Water heating 2 – switch on
ElH2
EH2
Heat pump 1 – digital compressor – switch on
HPwm1
HPM
Heat pump 2 – digital compressor – switch on
HPwm2
HP2M
Gas heating – switch on
Gs
G
Gas heating – increase output
GsM
GM
Gas heating – reduce output
GsL
GL
Water cooling – switch on
WtC
WC
Condensing unit - switch on globally
Cnd
Cd
Condensing unit 1 – cool
CndC
CdC
Condensing unit 1 – heat
CndH
CdH
Condensing unit 2 – cool
Cnd2C
Cd2C
Condensing unit 2 – heat
Cnd2H
Cd2H
Condensing unit 3 – cool
Cnd3C
Cd3C
Condensing unit 3 – heat
Cnd3H
Cd3H
Condensing unit 1 – switch on
Cnd1O
CdO
Condensing unit 2 – switch on
Cnd2O
Cd2O