specified in the frequency converter parameters. Therefore, the run-out values should be
the same.
Speed
(%,%,%)
– speed values for three-stage fan speed control by external contacts.
ModeSwitches
=
3xSpeed
must be set in the configuration.
MinSpeed
(36%)
– used to protect the motor against thermal overload when operating at
speeds lower than 18 Hz for long periods of time (36% is for the rated speed of 50 Hz).
This applies mainly to frequency converter controlled motors.
MaxSpeed
(100%)
– used to limit the fan power to prevent the individual
Comfort
and
Economy
regimes from setting fan power in excess of their operating point according to
the unit's technical specifications. A bigger amount of supply air can cause, for example,
incorrect operation of the manostats (exceeding the pressure drop) of filters,
recuperator, etc.
Delay
(30 s) –
delay of the supply fan switching on after the exhaust fan switching on. This
function is particularly important in a recuperator configuration where the warm air
supplied to the recuperator by the exhaust fan heats the recuperator before the supply
fan starts.
Release
(1 to 31) –
indication that the conditions for starting the AC unit fans have been met.
The value is given by the sum of the weights of all the 5 conditions with weights of 1 to 16.
The weights of the conditions needed to start the fans are in Tab. 1.
Condition
Weight
Condition description
1
1
There is no fault blocking the operation of the fans.
2
2
One of the operating regimes is selected (
Comfort
,
Economy
,
Tempering
, or
Freecooling
).
3
4
Unit operation is not blocked by another component
(service switch, boiler room, air flow sensor, etc.).
4
8
Standard operating requirement to turn on the fans
(
Heat
,
Cool
or
Ventilate
) that is not blocked by too low
or high supply air temperature.
5
16
Forced on fans with a higher priority than the standard
operating requirement (unit ventilation, poor air quality
or humidity, etc.).
Table 1 - Fan start release
Release
< 15 –
Fans are not running, all the necessary conditions are not met.
Release
= 15 –
Fans are running, all the necessary conditions are met.