KJM MANDÍK
–
Detailed operating instructions
M&C KJMPNO 07/2022
MANDÍK, a.s.,
70
X
– universal input to which an input function can be assigned. Several types of
resistor, voltage, current and digital sensors can be connected to this input. The
universal input can also be configured as a voltage, current or digital output, if
required.
B
– NTC10K temperature input.
D
– potential-free digital input.
Y
– analog output with 0-10V range.
Q
– relay output 230VAC, max. 3A/ 2A (cos 0.6).
y
–
is the serial number of the input or output on the controller or on the controller extension.
13
Assignment of inputs and outputs
The input and output assignment item is only accessible after service login. Here, the
assignment of controller inputs and outputs to temperature sensors, fans, filters, electric heating,
etc. is made according to the electrical drawings of the actual wiring. The settings are made at the
factory and can only be changed by a knowledgeable person, as incorrect settings may damage
the equipment or cause injury to the operator.
Assignment of analog inputs
13.1
The assignment of the digital and analog inputs is done separately for every component
(temperature, humidity, pressure, fan operation or malfunction, water heating, etc.). A
prerequisite for the correct function of the assigned input is the setting of the correct type of
connected sensor or input function in the
Inputs/Outputs
. The assignment of digital and analog
inputs is carried out according to the following examples:
Temperature sensor
– in the
AssignmentInputs/Outputs
Temperatures
menu, there for
the selected temperature, select one of the inputs marked according to the syntax described
in the previous chapter “Inputs and outputs”, (e.g. for a room temperature sensor connected
to 1 universal input of the controller, set
Room
= X1
). In addition to these inputs, the room
unit assignment is offered with the POL (POL822) and AMR (AMR-OP70) designations.
Another option is to assign a constant temperature via setting the input to
Set
.
The required