MANDÍK, a.s.,
76
assignments is given in Table 3. Another option is to assign a constant analog value (0-10V) in %
using the option
Set (1% = 0.1V).
The required value on this output is then set under the menu
SettingValues–Set
.
The example setting of 8.5V on analog output Y1 is done in two steps:
1.
AssigningOutputs:
AO.Y1 = Set.
2.
SettingValues–Set
:
AO.Y1 = 85%.
The component abbreviations in the table are also given for the previous SW version 28.01.
Device component name
Abbreviation
v28.01
Abbreviation
v29.01
Supply fan - speed
FanS
FS
Exhaust fan - speed
FanE
FE
Mixing damper - position
DmpM
DM
Recuperator - output
Rec
Rc
Water heating 2 – output
5
WH2
Water heating – output
WtH
WH
Electric heating 1 – output
ElH
EH
Electric heating 2 – output
ElH2
EH2
Supply air damper - position
DmpS
DS
Exhaust air damper - position
DmpE
DE
Gas heating – output
GasH
G
Gas heating bypass damper - position
DmpG
DG
Water cooling – output
WtC
WC
Condensing unit 1 – output
CndU1
Cd1U
Condensing unit 2 – output
CndU2
Cd2U
Condensing unit 3 – output
CndU3
Cd3U
Condensing unit 4 – output
CndU4
Cd4U
Heat pump circuit 1 – output
HPmp
HP
Heat pump circuit 2 – output
HPmp2
HP2
Humidifier – output
Hum
Hu
Condensing unit 1 – Heat/Cool (FDP3)
CndCH1
Cd1CH
Condensation unit 2 – Heat/Cool (FDP3)
CndCH2
Cd2CH
Condensation unit 3 – Heat/Cool (FDP3)
CndCH3
Cd3CH
Condensing unit 4 – Heat/Cool (FDP3)
CndCH4
Cd4CH
Condensing unit 1 – off = 1V, on = 9V
CndOn
Cd1O
Air flow controller 1 - position
AirFl1
AF1
Air flow controller 2 - position
AirFl2
AF2
Condensation unit 2 – off = 1V, on = 9V
28
Cd2O
Condensation unit 3 – off = 1V, on = 9V
29
Cd3O
Condensing unit 4 – off = 1V, on = 9V
30
Cd4O
Condensing unit 5 – off = 1V, on = 9V
Cd5O