KJM MANDÍK
–
Detailed operating instructions
M&C KJMPNO 07/2022
MANDÍK, a.s.,
57
displayed. A service signal may also be indicated on the controller's digital output. It is a
prerequisite that the internal time of the controller corresponds to real time.
ServiceLight
(
Shines
/
Flash
/
Fire&Smoke
)
– defines the function of the digital
Service
output that can be used to control the light signalling:
Shines
–
Service
digital output will be permanently switched on in the event of a
service signal.
Flash
– digital output
Service
will switch on with a period of 5 s in case of service
signalling.
AlarmLight
(
Shines
/
Flash
)
– defines the function of digital fault
A
output, which can be
used to control the light signalling:
Shines
– digital fault
A
output will be permanently switched on in the event of a fault
signal and will not differentiate between a detected fault and a new fault.
Flash
– digital fault
A
output will be switched on with a period of 1s in the event of a
fault signal and will not discriminate between a detected and a newly generated
fault.
Fire&Smoke
– digital fault
A
output will behave in the same way as the fault
indication on the display or HMI controller. In the event of a newly generated fault,
the digital output will switch on with a period of 1 s. In the event of a cleared fault,
the digital output will be permanently switched on.
DueDate
– this function enables automatic shutdown of the unit if an invoice is not paid
by the agreed date. Detailed instructions can be found in the separate manual “Invoice
due date tracking”.
NumberDays
– number of days until the invoice is due after which the unit will be
shut down is entered. In the factory setting,
NumberDays
is zero, and no invoice due
date is tracked.
DaysLeft
– displays the number of days until the unit is shut down due to non-
payment of the invoice.