KJM MANDÍK
–
Detailed operating instructions
M&C KJMPNO 07/2022
MANDÍK, a.s.,
77
Condensing unit 6 – off = 1V, on = 9V
Cd6O
Condensing unit 5 – output
Cd5U
Condensing unit 6 – output
Cd6U
Condensing unit 5 – Heat/Cool (FDP3)
Cd5CH
Condensing unit 6 – Heat/Cool (FDP3)
Cd6CH
Backup supply fan - speed
FS2
Backup exhaust fan - speed
FE2
Air flow controller 3 - position
AF3
Air flow controller 4 - position
AF4
Air quality – output
AQ
Table 4 - List of analog output assignment abbreviations
External switches
13.5
The external switches are configurable and fixed. Their assignment is the same as for other
digital inputs and is described in the chapter “Inputs and Outputs”.
13.5.1
Configurable external switches
These switches are used to switch the modes of the AC unit externally, and the specific
function of each is determined by the option in
Configuration
ModeSwitches
. Their function is
enabled in
ComponentsMachine
Others
.
1Switch
– is used depending on the
ModeSwitches
configuration:
Modes
– has the function of switching the AC unit to the
Economy
regime.
Modes2
–
has the function of switching the AC unit to the regime
Economy
.
2xMisto
– has the function of switching the AC unit to the regime
Economy
.
When
the
2Switch
contact is activated, it switches the AC unit from the
Economy
regime to
Comfort
.
3xSpeed
– has the function of switching the AC unit to the
Comfort
regime at speed
stage I.
2Switch
– is used depending on the
ModeSwitches
configuration:
Modes
– when the
1Switch
contact is activated, it switches the AC unit from the
Economy
regime to
Comfort
. When the
1Switch
contact is open, it has no function.
Modes2
– switches the AC unit to the
Comfort
regime regardless of the status of
1Switch
.