Detailed operating instructions
M&C KJMPNO 07/2022
MANDÍK, a.s.,
68
ComponentsMachine
Fans
Speed
.
The unit is turned on by turning on any
switch.
Freecooling
(
No
/
Yes
)
– enables the use of the venting function in the
Tempering
regime.
EnergyWatch
(
No
/
ElectricityMeter
/
Fan
)
– enables monitoring of energy consumption while
the unit is operating. It specifies how the electricity consumption is measured and calculates
the other energy consumption based on the temperature difference before and behind the
components.
ElectricityMeter
– separate electricity meter measures the total electricity
consumption of all the devices supplied from the switchboard.
Fan
– only the power consumption of fans is measured and the power consumption
of the switchboard can only be entered as a constant.
POL945
(
No
/1/2)
– allows the number of controller inputs to be expanded by one or two
POL945 modules with 8 Inputs/Outputs.
POL955
(
No
/1/2)
– allows to expand the number of controller inputs by one or two POL955
modules with 14 Inputs/Outputs.
POL985
(
No
/1/2)
– allows the number of controller inputs to be expanded by one or two
POL985 modules with 26 Inputs/Outputs.
AfterModificationOfValue
RestartRequired!
(
/
Execute
) –
the
Execute
option saves the
parameters to the controller's backup user memory. At the same time, the controller is
restarted to initialize the changes made.
ParametersLoad
(
/
Restore
)
– the
Restore
option loads the parameters from the backup user
memory of the controller. At the same time, the controller is restarted to initialize the
changes made.
OriginalSettings
(
/
Restore
)
– the
Restore
option is used to restore the original
configuration set at the factory. At the same time, the controller is restarted and the
production parameters are initialized.
11
Testing
The device testing item is only accessible after a service login. This function is intended for
service technicians during commissioning of the AC unit or during service inspections. The device