
IMPULSE•VG+ Series 3 Instruction Manual – 07/25/05
5-24
Load Check
Load Check function is a load-limiting feature that ensures the programmed load limit of the hoist is
not exceeded. It prevents the lifting (and potential loss) of a load that is overweight. When
IMPULSE•VG+ Series 3 detects an overload condition, it prevents any further raising. However, the
load can be lowered at the speed that is specified by constant C5-14 (Load Check Fault speeds).
NOTE:
Precautions should be taken when using load check where two or more hoists are used to
lift a single load.
Example: Use a normally closed relay from the load check output to break the raise (FWD Run)
command to the other hoist(s). This will insure that all hoists stop lifting if one hoist is
being overloaded.
Parameter
Code
Display
Function
Range
Initial Value
Access
Level
C5-01
Load Check 0/1
Determines whether Load
Check is enabled.
0
Adv
0
Disabled
1
Enabled
C5-02
LC Alarm Action
Action at Load Check alarm
or fault.
4
Adv
0
Alarm Only
1
Decel to Stop
2
Coast to Stop
3
Fault Stop
4
Use B3-03 Method (allows Lower only)
C5-03
Min Torque Ref
Minimum current/torque
reference during acceleration
that triggers Load Check.
0–100%
60
Adv
C5-04
Look Speed 1
First Load Check frequency
reference.
0–150 Hz
6
Adv
C5-05
I/T Ref for LS 1
Current/Trq Reference when
Fout or Fnfb - Look Speed 1
1-300%
160
Adv
C5-07
Look Speed 2
Second Load Check
frequency reference.
0–150 Hz
20
Adv
C5-08
I/T Ref for LS 2
Current/Trq Reference when
Fout or Fnfb - Look Speed 2
1-300%
160
Adv
C5-09
Look Speed 3
Third Load Check frequency
reference.
0–150 Hz
40
Adv
C5-10
I/T Ref for LS 3
Current/Trq Reference when
Fout or Fnfb - Look Speed 3
1-300%
160
Adv
C5-11
I/T Ref for > LS 3
Load Check Current when
Output Frequency > Look
Speed 3.
1-300%
160
Adv
C5-12
LC Holding Time
Time for holding Output
Frequency to stabilize Output
Current.
0.00–2.55
sec
1.00
Adv
C5-13
LC Testing Time
Time (after the LC Setting
Time) for comparing Output
Current with Reference
Current
0.00–2.55
sec
0.25
Adv
C5-14
LC Fault Speed
Maximum lowering speed
after Load Check fault
0–30 Hz
6.0
Adv
Summary of Contents for IMPULSE VG+ Series 3
Page 1: ...Software 8001 X July 2005 Part Number 140 10257 Copyright 2005 Magnetek Instruction Manual...
Page 6: ...c h a p t e r 1 Introduction...
Page 7: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 1 2 This page intentionally left blank...
Page 14: ...c h a p t e r 2 Installation...
Page 15: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 2 2 This page intentionally left blank...
Page 23: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 2 10 This page intentionally left blank...
Page 24: ...c h a p t e r 3 Wiring...
Page 25: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 3 2 This page intentionally left blank...
Page 40: ...c h a p t e r 4 Programming Basic Features...
Page 41: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 4 2 This page intentionally left blank...
Page 54: ...c h a p t e r 5 Programming Advanced Features...
Page 55: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 5 2 This page intentionally left blank...
Page 149: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 5 96...
Page 150: ...Troubleshooting IMPULSE VG Series 3 c h a p t e r 6...
Page 151: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 6 2 This page intentionally left blank...
Page 170: ...A p p e n d i x A IMPULSE VG Series 3 Parameter Listing...
Page 171: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 A 2 This page intentionally left blank...
Page 183: ...IMPULSE VG Series 3 Instruction Manual 07 25 05 A 14...