27
3.4
V/f PATTERN
These constants define the V/f pattern,
and are related to each other as shown
below.
NOTES:
1.
Where two setting ranges and two factory settings are listed
for a constant, the upper ones are for a 230V drive and the
Constants
no-02
thru
no-08
CONSTANT
DATA NAME
SETTING
RANGE
(NOTE 1)
FACTORY
SETTING
(NOTE 1)
no-02
Maximum Frequency ( Fmax )
50.0 - 400.0 ( Hz )
60.0
no-03
Maximum Voltage ( Vmax )
0.1 - 255.0 ( V )
230.0
0.1 - 510.0 ( V )
460.0
no-04
Maximum Voltage Frequency
( Fa )
0.2 - 400.0 ( Hz )
60.0
no-05
Frequency Midpoint ( Fb )
0.1 - 399.9 ( Hz )
1.5
no-06
Voltage Midpoint ( Vc )
0.1 - 255.0 ( V )
12.0
0.1 - 510.0 ( V )
24.0
no-07
Minimum Output Frequency
( Fmin )
0.1 - 10.0 ( Hz )
1.5
no-08
Minimum Output Frequency
Voltage ( Vmin )
0.1 - 50.0 ( V )
12.0
0.1 - 100.0 ( V )
24.0
OUTPUT
VOLTAGE
Vmax
(
no-03 )
Vc
(
no-06 )
Vmin
(
no-08 )
Fmin
Fb
Fa
Fmax
(
no-07 )
(
no-05 ) ( no-04 )
(
no-02 )
OUTPUT FREQUENCY
efesotomasyon.com - Yaskawa ac drive,servo motor
Summary of Contents for GPD 333
Page 1: ...Magne Tek GPD 333 Technical Manual efesotomasyon com Yaskawa ac drive servo motor ...
Page 3: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 6: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 14: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 15: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 16: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 17: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 61: ...48 This page intentionally left blank efesotomasyon com Yaskawa ac drive servo motor ...
Page 76: ...62 This page intentionally left blank efesotomasyon com Yaskawa ac drive servo motor ...
Page 78: ...efesotomasyon com Yaskawa ac drive servo motor ...