ELECTRICAL INSTALLATION.
The GPD 333
leaves the factory with all constants set for 2-Wire external ref-
erence control. Figure 1–5 must be used for all external con-
nections.
To use the GPD 333 in a 3-Wire application, drive constants
no-00
and
no-01
must be reprogrammed, using the optional
Digital Operator, Model DS039. Figure 1-6 must then be used
for all external connections.
CAUTION
Use only UL listed or CSA certified closed loop (ring lug) con-
nectors sized for the selected wire gauge. The connectors are
to be installed using the correct crimp tool recommended by the
connector manufacturer.
WIRE SIZE
TERMINAL
SCREW
CLOSED-LOOP
CONNECTOR
AWG
mm
2
20
0.5
M3
1.25 - 3.5
18
0.75
M4
1.25 - 4
16
1.25
14
2
M4
2 - 4
M5
2 - 5
12
3.5
M4
3.5 - 4
M5
3.5 - 5
10
5.5
M4
4 - 5.5
M5
5 - 5.5
efesotomasyon.com - Yaskawa ac drive,servo motor
Summary of Contents for GPD 333
Page 1: ...Magne Tek GPD 333 Technical Manual efesotomasyon com Yaskawa ac drive servo motor ...
Page 3: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 6: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 14: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 15: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 16: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 17: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 61: ...48 This page intentionally left blank efesotomasyon com Yaskawa ac drive servo motor ...
Page 76: ...62 This page intentionally left blank efesotomasyon com Yaskawa ac drive servo motor ...
Page 78: ...efesotomasyon com Yaskawa ac drive servo motor ...