44
3.20
OVERTORQUE DETECTION – CONTINUED
Overtorque Detection
Level
This is the reference
point for determining that an overtorque condition exists. Set
as a percent of GPD 333 rated current (see paragraph 3.8).
Overtorque Detection
Time
Determines how long
an overtorque condition must exist before another event will
occur, i.e. coast stop, multi-function output change of state, or
oL3
warning or fault displayed.
3.21
CARRIER FREQUENCY
The user can select a higher or lower carrier frequency,
depending on allowable operating noise levels for the applica-
tion. Adjusts in increments of 2.5 kHz (set value x 2.5 kHz =
carrier frequency).
NOTE: Also see paragraph 1.4.4.
IMPORTANT:
Setting
5
or
6
will reduce maximum
continuous output current of the GPD 333.
• Constant
no-44
: NOT USED.
• Constant
no-45
: see paragraph 3.10.
SETTING
MAXIMUM CONTUINUOUS OUTPUT CURRENT
1 to 4
Up to 100% of GPD 333 output current
5
Up to 90% of GPD 333 output current
6
Up to 80% of GPD 333 output current
Constant
no-41
Range : 30 to 200 ( % )
Factory Setting : 160
Constant
no-42
Range : 0.1 to 10.0 ( s )
Factory Setting : 0.1
Constant
no-43
Range : 1 to 6 ( x 2.5 kHz )
Factory Setting : 4 ( = 10 kHz )
efesotomasyon.com - Yaskawa ac drive,servo motor
Summary of Contents for GPD 333
Page 1: ...Magne Tek GPD 333 Technical Manual efesotomasyon com Yaskawa ac drive servo motor ...
Page 3: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 6: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 14: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 15: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 16: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 17: ...efesotomasyon com Yaskawa ac drive servo motor ...
Page 61: ...48 This page intentionally left blank efesotomasyon com Yaskawa ac drive servo motor ...
Page 76: ...62 This page intentionally left blank efesotomasyon com Yaskawa ac drive servo motor ...
Page 78: ...efesotomasyon com Yaskawa ac drive servo motor ...