26
3.3
OPERATION SIGNAL SELECTION 1
This four-digit binary
code determines the
source of frequency reference, Run/Stop signals,
the method of stopping the motor when the Stop command is
issued, and whether the output voltage limiter is enabled or
disabled.
DIGIT
FUNCTION
X X X X
0 = External frequency reference
( 0-10Vdc or 4-20mA ) (Term. 8 or 9)
1 = Internal Frequency Reference
( set by Digital Operator )
X X X X
0 = External Run / Stop commands
1 = Run / Stop by Digital Operator
X X X X
0 = Ramp to stop at Stop command
1 = Coast stop at Stop command
X X X X
0 = V/f with output voltage limiter
1 = V/f without output voltage limiter
Constant
no-01
Factory Setting : 0000
Note: If X X X X is set to
1
, the V/f pattern (see para-
graph 3.4) must be set to match motor data.