73VR2102 / 73VR2104 / 73VR2106 / 73VR2108 / 73VR2110 / 73VR2112 USERS MANUAL EM-7395-B Rev.24
Note
‘e’ can be used to input an exponential value such as ‘1e9.’ Entering ‘e’ in any other way (e.g. ‘1ee’)
will not be recognized as a numeral.
Scale shift
Plot positions can be shifted in parallel on the trend chart. This function is useful when multiple graphs are overlapping.
You can separate the plot positions while no other data is changed. Refer to Section “5.5.1 PEN SETTING (INPUT)”.
Normal / Log
When Normal plotting is selected, the plot area is divided equally. When Logarithmic 1 is selected, the plot area is
divided in specified scale of exponents of 10.
For Logarithmic plotting, specify the lower limit of exponent in ‘Logarithmic Plot Position Exponent’ field within -9 to
8, and how many divisions you wish to have in ‘Exponential Scale’ among 10, 5, 4, 2, and 1. Refer to Section “5.5.1
PEN SETTING (INPUT)”.
n
FILTER FUNCTIONS
Touching Pen setting (Func) and choosing one of the pens specified as analog channel opens the Pen setting (Func)
view for the selected. Filter function views are as follows:
Moving average.
First order lag filter.
Moving Average
Specify number of samples used for the moving average operation and an input channel. Touching Inp.1 opens the
Tag name selector view. Select an input signal used for the operating function.
Samples
Specify between 2 and 16
First Order Lag Filter
Specify a time constant and an input channel. Touching Inp.1 opens the Tag name selector view. Select an input
signal used for the operating function.
Time constant
Specify between 0.00 and 100.00 seconds. Max. 2 decimal places.