LOGIC FUNCTIONS
Function
Choosing one of the available functions will change the rest of the parameter list to match the selected function.
Input (X1, X2)
Touching Inp.1 or Inp.2 opens the Tag name selector view. Select input signals used for the operating function.
Caution !
Be careful to choose a pen of Not Itself. For example, you cannot choose Function Pen 1 or the last
data of Function Pen 1 to be used in an equation for Function Pen 1.
Initial value
Initial value is used in the function operation cycle as default data sample when ‘last’ data is specified in an equation.
If you do not need, leave the field blank.
Initial value
1 for ON, 0 for OFF
Caution !
Any setting other than 0 and 1 will be handled as 0 as initial value.
For the XOR function, setting other than 0 and 1 to X1 or X2 will result in ‘0.’
OFF Description, ON Description
Short description for ON (1) and OFF (0) status for the operation result can be specified.
OFF description
Max. 5 characters
ON description
Max. 5 characters
n
ANEMOSCOPE
Input (X1)
Touching Inp.1 opens the Tag name selector view. Select input signals used for the operating function.
Caution !
Be careful to choose a pen of Not Itself. For example, you cannot choose Function Pen 1 or the last
data of Function Pen 1 to be used in a equation for Function Pen 1.
5.6 HARDWARE CONFIGURATION
The initial view for the Hardware Configuration setting is as shown below.
5.6.1 ADC SPEED
Choose from Fast, Slow and Medium. When 100 msec. storing rate is selected, there is no need of this setting.
5.6.2 LINE NOISE FILTER
Choose from 50/60 Hz, 50 Hz or 60 Hz. When 100 msec. storing rate is selected, there is no need of this setting.
Caution !
When the line noise filter setting is changed, measured values immediately after the change may
contain errors by the AD conversion cycle change. Wait for 10 seconds before resuming data record-