Lucent Technologies 415B Battery Plant for 4ESS
7 - 18 Retrofit of 415A Battery Plant
Issue 6 September 1999
Alarm
Connections
The alarm connections from the 415B to the 415A Control and
Distribution Bays are wired in parallel using 807A 16/26 SWBD
(comcode 105412480).
Table 7-A shows the connections required between the 415A
and 415B frames.
Note
Connection of the alarms should be made after the test is
complete. If connected prior to testing, alarms will be
issued to the alarms centers.
Table 7-A: BJT1 Connections
Alarm
415B
415A
Color
Pin
Color
Pin
HV
R/G
1
TB3
R/G
11
TB4
G/R
17 G/R
13
PMJA
W/O
4
TB2
W/O
9
O/W
20
O/W
10
PMJV
W/S
5 W/S
26
S/W
21 S/W
25
PMNA
W/BR
7 W/BR
4
BR/W
23 BR/W
5
PMNV
R/BL
8 R/BL
28
BL/R
24 BL/R
30
DISCHG FA
W/G
11
W/G
6
G/W
27 G/W
8
FA
W/BL
12 W/BL
1
BL/W
28 BL/W
3
BD
R/O
13
R/O
16
O/R
29 O/R
l8
ACF
R/BR
14 R/BR
14
BR/R
30
BR/R
15
VLV
R/S
16
R/S
21
S/R
32
S/R
23
RFA
BL/BK
15
BL/BK
12
TB1
BK/BL
31
BK/BL
13