Lucent Technologies 415B Battery Plant for 4ESS
Issue 6 September 1999
Retrofit of 415A Battery Plant 7 - 53
Table 7-F lists the optional circuit packs/kits.
The Galaxy Controller is configured at the factory. Refer to the
section on Configuration in the Galaxy Controller product
manual (Select Code 167-792-122).
The following list gives some of the more important Galaxy
information that is needed in order to check the configuration.
Table 7-E: Circuit Packs/Kit Furnished with the
Galaxy Controller
Power Supply
BJJ1
Independent Controller
BJB2
Intelligent Controller
BJH3
Remote Peripheral Monitor (RPM) Interface
BJM1
Fuse Board
BJF4
Terminal Board
BJT1
Display
BJG1
Alarm Board
BJE1
Rectifier Interface
BJC1
Basic Power Board
BJA1
Battery Reserve Time Prediction Kit
K1
Table 7-F: Optional Circuit Packs
for the Galaxy Controller
Modem
BJL2
Data Switch
BJK1
Rectifier
J87132B-2
Plant Shunt
600 amperes @ 50 mV
High Voltage Shutdown
156.5V
Boost High Voltage Shutdown
160V
Backup High Voltage Shutdown
156.9V
High Float Warning
155.5V
Rectifier on Threshold (ROT)
130V
High Float Warning (Boost)
159V
Battery on Discharge (BD)
149V
Battery on Discharge (BD Boost)
149V
Very Low Voltage (VLV)
133V
Power Distribution Frame Shunts
150 amperes @ 50 mV
Float Voltage
151.9V
Boost Voltage
156V