Parameter Description Set Meaning
P201.01 Frequency setpoint source 5 Setpoint specified via network
P201.02 PID setpoint source 5 PID setpoint specified via network
P400.37 Network enable 1 Network enabled
P510.01 Serial node address 1-255 Modbus serial node
P510.02 Baud rate 5 38400bps
P510.03 Data format 1 8 data bits, even parity, 1 stop bit
P515.01 Response to timeout 0 No response
P530.01 Modbus parameter 1 P123.00 Motor temperature
P530.02 Modbus parameter 2 P108.01 Output power
P530.03 Modbus parameter 3 P121.01 PID setpoint
P530.04 Modbus parameter 4 P121.02 PID feedback
P530.05 Modbus parameter 5 P121.03 PID status
P530.06 Modbus parameter 6 P151.01 Operating time
P530.07 Modbus parameter 7 P107.00 Actual Torque
P530.08 Modbus parameter 8 P210.00 Min frequency
P530.09 Modbus parameter 9 P211.00 Max frequency
P530.10 Modbus parameter 10 P605.01 PID, min value
P530.11 Modbus parameter 11 P605.02 PID, max value
P530.12 Modbus parameter 12 P400.37 Network control enable
P530.13 Modbus parameter 13 P201.01 Frequency setpoint source
P530.14 Modbus parameter 14 P201.02 PID setpoint source
P530.15 Modbus parameter 15 P102.00 Actual frequency setpoint
P530.16 Modbus parameter 16 P121.01 Actual PID setpoint
P600.01 PID enable 0 o 1 0 = PID control disabled, 1 = PID control enabled
NOTE.
– To communicate with the EXCRDU1 remote keypad, all the above parameters (except for the serial node address, which can be modified as you prefer) must be set to the value indicated in the table.
– In the case of use of PID control, if you follow the above configuration, the feedback signal must be connected to the first analog input AI1 of the VLB3.
5.6.8 Common error codes
Error code Description Possible causes Remedy
0x2350 Motor overload (i
2
*t) Motor thermally overloaded. Possible causes: – Check drive dimensioning.
– Impermissible continuous current. – Check machine/driven mechanics for excessive load.
– Too frequent acceleration processes.
– Too long acceleration processes.
0x2320 Short circuit/earth leakage – Short circuit/earth fault of motor cable – Check motor cable.
– Capacitive charging current of the motor cable too high. – Check length of the motor cable.
– Use shorter or lower-capacitance motor cable.
0x2382 I*t error Device utilisation (I*t) too high by frequent and too long – Check drive dimensioning.
acceleration processes.
0x3210 DC bus overvoltage DC-bus voltage has exceeded the error threshold for – Reduce dynamic performance of the load profile.
overvoltage (display in parameter P208.06, results from the – Check mains voltage.
setting of the rated mains voltage in P208.01). – Check settings for the brake energy management
Possible causes: (see chapter Brake energy management on I473
– Too high braking energy. instruction).
– Too high mains voltage. – Connect brake resistor to the power unit and activate the
integrated brake chopper.
– Reduce the slip compensation gain: set P315.01=5%.
0x3220 DC bus undervoltage DC-bus voltage has fallen below the error threshold for – Check mains voltage.
undervoltage (display in parameter P208.03, results from – Check DC-bus voltage (see P105.00).
the setting of the rated mains voltage in P208.01). – Check mains settings (see P208.01).
0x4210 Power unit overtemperature The heatsink temperature of the power unit (display in – Provide for a sufficient cooling of the device.
P117.01) has exceeded the fixed error threshold 100°C. – Clean fan and ventilation slots.
Possible causes: – If required, replace fan.
– Ambient temperature too high. – Reduce switching frequency in P305.00.
– Fan or ventilation slots are polluted.
– Fan is defective.
0x4310 Motor overtemperature The PTC motor temperature sensor connected to terminals – Check drive dimensioning.
T1-T2 measures a too high motor temperature. – Check the presence of the X109 terminal block and the
Possible causes: wiring of the terminals T1- T2: if any PTC motor
– Motor too hot by impermissibily high currents. temperature sensor is connected, is necessary to make a
– Motor too hot by frequent and too long acceleration jumper between terminals T1-T2 or disable the motor
processes. temperature monitoring by setting P309.02=0.