5.4.7 With Modbus communication protocol
Parameter Function Setting Description
P210.00 Minimum frequency 0Hz Insert the value of the minimum frequency
P211.00 Maximum frequency 50Hz Insert the value of the maximum frequency
P220.00 Acceleration time 5sec Insert the value of the acceleration time
P221.00 Deceleration time 5sec Insert the value of the deceleration time
P400.37 Activate network control 1 Network control activated
P510.01 Modbus node ID 1 Insert the node ID
P510.02 Baud rate 4 Select the baudrate (e.g. “4” means a baudrate of 19200 bps)
P510.03 Data format 1 Definition of the data format (e.g: “1” means “8/E/1”: 8 data bits, Even parity,
1 stop bit)
P515.01 Response to time-out 0 No action in case of Modbus time-out
5.4.8 PID Control - Setpoint adjusted with keypad and feedback signal type 0-10V
Parameter Function Setting Description
P201.02 PID setpoint source 1 PID setpoint adjusted from keypad
P210.00 Minimum frequency 30Hz Insert the value of the minimum frequency
P211.00 Maximum frequency 50Hz Insert the value of the maximum frequency
P220.00 Acceleration time 5sec Insert the value of the acceleration time
P221.00 Deceleration time 5sec Insert the value of the deceleration time
P430.01 Analog input 1 (AI1) configuration 0 Analog signal type 0-10V
P600.01 PID enable 1 PID function enabled
P600.02 PID feedback source 1 PID feedback connected to analog input AI1
P610.01 PID sleep mode activation 1 PID sleep mode enabled. Sleep mode is activated when the frequency is less than
P610.03 for a time longer than P610.05
P610.03 PID sleep mode: frequency treshold 35Hz See description of P610.01 parameter
P610.05 PID sleep mode: delay time 5sec See description of P610.01 parameter
5.4.9 PID Control - Setpoint adjusted with keypad and feedback signal type 4-20mA
Parameter Function Setting Description
P201.02 PID setpoint source 1 PID setpoint adjusted from keypad
P210.00 Minimum frequency 30Hz Insert the value of the minimum frequency
P211.00 Maximum frequency 50Hz Insert the value of the maximum frequency
P220.00 Acceleration time 5sec Insert the value of the acceleration time
P221.00 Deceleration time 5sec Insert the value of the deceleration time
P430.01 Analog input 1 (AI1) configuration 4 Analog signal type 4-20mA
P600.01 PID enable 1 PID function enabled
P600.02 PID feedback source 1 PID feedback connected to analog input AI1
P610.01 PID sleep mode activation 1 PID sleep mode enabled. Sleep mode is activated when the frequency is less than
P610.03 for a time longer than P610.05
P610.03 PID sleep mode: frequency treshold 35Hz See description of P610.01 parameter
P610.05 PID sleep mode: delay time 5sec See description of P610.01 parameter
5.4.6 From motor potentiometer (MOP)
If the motor potentiometer is active as setpoint source, the frequency setpoint can be changed via the triggers assigned to two input contacts configured with the functions "MOP UP" (increase frequency) and "MOP
DOWN" (decrease frequency).
Parameter Function Setting Description
P400.04 Reset fault function (default: DI2) 0 Disable the reset fault function
P400.13 Reverse rotation function (default: DI3) 0 Disable the reverse rotation function
P400.23 Motor potentiometr UP function 12 DI2 = MOP UP function
P400.24 Motor potentiometr DOWN function 13 DI3 = MOP DOWN function
P400.25 Enable motor potentiometer as setpoint 1 MOP is used as frequency setpoint
P413.00 Motor potentiometr starting mode 0 The last MOP value is used as initial value
NO
COM
NC
24E
GND
AI1
AI2
AO1
10V
24V
DI1
DI2
DI3
DI4
DI5
DO1
GND
24E
MOP UP
MOP DOWN