I472 GB I 01 19
31100284
6
G
B
3.2 FUSES AND CABLE CROSS-SECTIONS
Rated power kW 0.4 0.75
Cable installation in compliance with EN 60204-1
Laying system B2
Operation Without mains choke
Fuse
Characteristics gG/gL or gRL
Max. rated current A 10
Circuit breaker
Characteristics B
Max. rated current A 10
Operation With mains choke
Fuse
Characteristics gG/gL or gRL
Max. rated current A 10
Circuit breaker
Characteristics B
Max. rated current A 10
Earth-leakage circuit breaker
3-phase mains connection
≥
30 mA, type B
Mains connection
Connection X100
Connection type Screw terminal
Min. cable cross-section mm² 1
Max. cable cross-section mm² 2.5
Stripping length mm 8
Tightening torque Nm 0.5
Required tool 0.5 x 3.0
Motor connection
Connection X105
Connection type Screw terminal
Min. cable cross-section mm² 1
Max. cable cross-section mm² 2.5
Stripping length mm 8
Tightening torque Nm 0.5
Required tool 0.5 x 3.0
PE connection
Connection PE
Connection type PE screw
Min. cable cross-section mm² 1
Max. cable cross-section mm² 6
Stripping length mm 10
Tightening torque Nm 2
Required tool Torx 20