Rated power kW 5.5 7.5 11 15
Cable installation in compliance with EN 60204-1
Laying system B2
Operation Without mains choke
Fuse
Characteristics gG/gL or gRL
Max. rated current A 25 32 32 63
Circuit breaker
Characteristics B
Max. rated current A 25 32 32 63
Operation With mains choke
Fuse
Characteristics gG/gL or gRL
Max. rated current A 25 32 32 63
Circuit breaker
Characteristics B
Max. rated current A 25 32 32 63
Earth-leakage circuit breaker
3-phase mains connection
≥
300 mA, type B
Mains connection
Connection X100
Connection type Screw terminal
Min. cable cross-section mm² 1.5
Max. cable cross-section mm² 6 16 35
Stripping length mm 9 11 18
Tightening torque Nm 0.5 1.2 3.8
Required tool 0.6 x 3.5 0.8 x 4.0 0.8 x 5.5
Motor connection
Connection X105
Connection type Screw terminal
Min. cable cross-section mm² 1.5
Max. cable cross-section mm² 6 16 35
Stripping length mm 9 11 18
Tightening torque Nm 0.5 1.2 3.8
Required tool 0.6 x 3.5 0.8 x 4.0 0.8 x 5.5
PE connection
Connection PE
Connection type PE screw
Min. cable cross-section mm² 1.5 1.5 1.5
Max. cable cross-section mm² 6 16 25
Stripping length mm 10 11 16
Tightening torque Nm 2 3.4 4
Required tool Torx 20 PZ2