B
Rated power kW 45 55 75
Cable installation in compliance with EN 60204-1
Laying system C F
Operation
Fuse
Characteristics -
Max. rated current A - - -
Circuit breaker
Characteristics -
Max. rated current A - - -
Operation With mains choke
Fuse
Characteristics gG/gL or gRL gR
Max. rated current A 125 160
Circuit breaker
Characteristics B -
Max. rated current A 125 - -
Earth-leakage circuit breaker
3-phase mains connection
≥
300 mA, type B
Mains connection
Connection X100
Connection type Screw terminal
Min. cable cross-section mm² 10 25
Max. cable cross-section mm² 50 95
Stripping length mm 19 22
Tightening torque Nm 4 10
Required tool Allen key 4.0 Allen key 6.0
Motor connection
Connection X105
Connection type Screw terminal
Min. cable cross-section mm² 10 25
Max. cable cross-section mm² 50 95
Stripping length mm 19 22
Tightening torque Nm 4 10
Required tool Allen key 4.0 Allen key 6.0
PE connection
Connection PE
Connection type PE screw
Min. cable cross-section mm² 1.5 4
Max. cable cross-section mm² 25 25
Stripping length mm 16 16
Tightening torque Nm 4 4
Required tool PZ2 PZ2