Rated power kW 1.5 2.2 4
Cable installation in compliance with EN 60204-1
Laying system B2
Operation Without mains choke
Fuse
Characteristics gG/gL or gRL
Max. rated current A 16 16 25
Circuit breaker
Characteristics B
Max. rated current A 16 16 25
Operation With mains choke
Fuse
Characteristics gG/gL or gRL
Max. rated current A 16 16 25
Circuit breaker
Characteristics B
Max. rated current A 16 16 25
Earth-leakage circuit breaker
3-phase mains connection
≥
30 mA, type B
≥
300 mA, type B
Mains connection
Connection X100
Connection type Screw terminal Screw terminal
Min. cable cross-section mm² 1 1.5
Max. cable cross-section mm² 2.5 6
Stripping length mm 8 9
Tightening torque Nm 0.5
Required tool 0.5 x 3.0 0.6 x 3.5
Motor connection
Connection X105
Connection type Screw terminal Screw terminal
Min. cable cross-section mm² 1 1.5
Max. cable cross-section mm² 2.5 6
Stripping length mm 8 9
Tightening torque Nm 0.5
Required tool 0.5 x 3.0 0.6 x 3.5
PE connection
Connection PE
Connection type PE screw
Min. cable cross-section mm² 1 1.5
Max. cable cross-section mm² 6 6
Stripping length mm 10 10
Tightening torque Nm 2 2
Required tool Torx 20