Commissioning
5-8
BA9300SU EN 2.1
5.3
Controller enable
•
The controller is enabled only after all sources of controller inhibit have been reset (series
connection of all sources).
– When the controller is enabled, the green LED on the controller is illuminated.
•
The active sources of the controller inhibit are displayed under C0183 (see also menu:
Diagnostic; Actual info.
The following table shows the conditions for controller enable:
Source controller inhibit
Controller inhibited
Controller enabled
Note
Terminal X5/28
0 V
...
+ 4 V
+ 13 V
...
+ 30 V
-
Keypad
STOP key
RUN key
Inhibit with the STOP key is possible
only if the STOP key is assigned with
”CINH” under C0469.
Error
In case of TRIP
In case of Message
TRIP reset
For check see chapter 9
System bus
Transmission of the control information
INHIBIT via C0135
Transmission of the control information
ENABLE via C0135
see Manual
Fieldbus module
See Operating Instructions of the corresponding fieldbus module
-
Note!
All sources act like a series connection of switches which are independent of each other.
5.4
Input of the direction of rotation
Based on the factory setting, the motor direction of rotation depends on
•
the sign of the speed setpoint (link of main and additional setpoint).
•
the triggering of the digital inputs X5/E1 and X5/E2.
Summary of Contents for EVS9321-CS
Page 3: ...Operating Instructions EDB9300UES 00414796 Global Drive 9300 servo ...
Page 21: ...Technical data 3 8 BA9300SU EN 2 1 ...
Page 57: ...Installation 4 36 BA9300SU EN 2 1 ...
Page 73: ...During operation 6 4 BA9300SU EN 2 1 ...
Page 117: ...Troubleshooting and fault elimination 9 10 BA9300SU EN 2 1 ...
Page 119: ...Maintenance 10 2 BA9300SU EN 2 1 ...
Page 188: ...Appendix 11 69 BA9300SU EN 2 1 ...
Page 189: ...Appendix 11 70 BA9300SU EN 2 1 ...