Installation
4-11
BA9300SU EN 2.1
4.2.2
Protection of the controller
Stop!
The controllers contain electrostatically sensitive components.
•
Prior to assembly and service operations, the personnel must be free of electrostatic charge:
– Discharge by touching the PE fixing screw or another grounded metal part in the control
cabinet.
•
Length of the screws for the connection to the screen cable/screen plate for the types 9327
to 9332: < 12 mm
•
Controller protection by means of external fuses.
(
^
3-6)
•
Protect unused control inputs and outputs with plugs or covers (included in the contents of
delivery) for the Sub-D inputs.
•
Frequent mains switching can overload the internal switch-on current limitation. For cyclic
mains switching, the controller can be switched on every three minutes as a maximum.
•
The controllers 9324, 9326, 9328 and 9329 must only be operated with the appropriate mains
filters.
(
^
3-7)
•
In case of condensation, connect the controller to the mains voltage only after the visible
humidity has evaporated.
4.2.3
Motor protection
•
Complete motor protection according to VDE:
– By overcurrent relays or temperature monitoring.
– Required for group drives (motors connected in parallel to a controller)
– We recommend the use of PTC thermistors or thermostats with PTC characteristic to
monitor the motor temperature.
Stop!
As standard Lenze three-phase AC motors are equipped with PTC thermistors. If motors from other
manufacturers are used, carry out all steps required for the adaptation to the controller.
(
^
4-28)
•
When using motors with insulation which is not suitable for inverter operation:
– Please contact your motor supplier.
Lenze AC motors are designed for inverter operation.
•
With the corresponding parameter setting, the controllers generate field frequencies up to
600 Hz:
– With motors not suited for the application, dangerous overspeeds may occur and destroy
the drive.
Summary of Contents for EVS9321-CS
Page 3: ...Operating Instructions EDB9300UES 00414796 Global Drive 9300 servo ...
Page 21: ...Technical data 3 8 BA9300SU EN 2 1 ...
Page 57: ...Installation 4 36 BA9300SU EN 2 1 ...
Page 73: ...During operation 6 4 BA9300SU EN 2 1 ...
Page 117: ...Troubleshooting and fault elimination 9 10 BA9300SU EN 2 1 ...
Page 119: ...Maintenance 10 2 BA9300SU EN 2 1 ...
Page 188: ...Appendix 11 69 BA9300SU EN 2 1 ...
Page 189: ...Appendix 11 70 BA9300SU EN 2 1 ...