Technical data
Supply concept of control voltage
External supply voltage 24 V
63
EDS84DPS424 EN 5.0
X11
Pin / Name
Feature
Rated value
11 / 24E
12 / GND
Connection for an external 24 V
supply voltage (loop−through
arrangement)
24 V according to IEC 61131−2 (cp. X10)
Number of devices included in the
loop−through arrangement
is limited by the voltage drop due to max. current= 10 A
and max. cable cross−section = 2.5 mm
2
Max. load for plug contacts
10 A
X4x, X50/X8x
Pin / Name
Feature
Rated value
1 / 24O
3 / GIO
24 V supply of the external sensors or
potential−free contacts
External supply at 24E: voltage drop < 2.5 V
Internal supply: DC 18 ... 28 V
Max. output current
200 mA per output
Total current for X4x, X50/X8x
1 A
Electric strength of external voltage
+30 V
Excess current release
Automatically resettable