Electrical installation − HighLine/StateLine version
Important notes
74
EDS84DPS424 EN 5.0
Stop!
No device protection if the mains voltage is too high
The mains input is not internally fused.
Possible consequences:
ƒ
Destruction of the device if the mains voltage is too high.
Protective measures:
ƒ
Observe the maximally permissible mains voltage.
ƒ
Fuse the device correctly on the supply side against mains fluctuations and
voltage peaks.
Stop!
The device contains components that can be destroyed by electrostatic
discharge!
Before working on the device, the personnel must ensure that they are free of
electrostatic charge by using appropriate measures.
Stop!
Pluggable terminal strips or plug connections
Plugging or removing the terminal strips or plug connections during operation
may cause high voltages and arcing.
Possible consequences:
ƒ
Damage of the devices
Protective measures:
ƒ
Switch off device.
ƒ
Only plug or remove the terminal strips or plug connections in deenergised
status.
Note!
Switching on the controller motor side is permissible for safety shutdown
(emergency stop) and for operation of several motors on the controller in V/f
operating mode.
Please observe the following:
ƒ
When switching with the controller is enabled, you can activate monitoring
functions of the controller. If no monitoring function is activated, switching
is permissible.
ƒ
The switching elements at the motor end must be rated for DC voltages
V
DCmax
= 800 V.
Summary of Contents for 8400 protec
Page 2: ...0Fig 0Tab 0...
Page 190: ...Appendix Declarations and certificates 13 190 EDS84DPS424 EN 5 0...
Page 191: ...Appendix Declarations and certificates 13 191 EDS84DPS424 EN 5 0...
Page 192: ...Appendix Declarations and certificates 13 192 EDS84DPS424 EN 5 0...
Page 193: ...Appendix Declarations and certificates 13 193 EDS84DPS424 EN 5 0...
Page 194: ...Appendix Declarations and certificates 13 194 EDS84DPS424 EN 5 0...