Technical data
Rated data
Operation at rated mains voltage 400 V
48
EDS84DPS424 EN 5.0
4.2.2
Operation at rated mains voltage 400 V
Basis of the data
Mains
Voltage
Voltage range
Frequency range
U
Lrated
[V]
U
Lrated
[V]
f [Hz]
3/PE AC
400
320 − 0 % ... 440 + 0 %
45 − 0 % ... 65 + 0 %
Mains current
Output power
Motor power
at I
arated
U, V, W
4 pol. ASM
Type
I
Lrated
[A]
S
arated
[kVA]
P
arated
[kW]
E84Dxxxx7514
4.1
1.5
0.75
E84Dxxxx1524
5.5
2.4
1.5
E84Dxxxx3024
9.7
4.6
3.0
E84Dxxxx4024
12.9
5.9
4.0
E84DHxxx7524
20.8
10.0
7.5
Output currents [A] at switching frequency
2 kHz
4 kHz
8 kHz
16 kHz
Type
I
arated2
I
aM2
I
arated4
I
aM4
I
arated8
I
aM8
I
arated16
I
aM16
E84Dxxxx7514
2.4
4.8
2.4
4.8
2.4
4.8
1.6
4.0
E84Dxxxx1524
3.9
7.8
3.9
7.8
3.9
7.8
2.3
6.4
E84Dxxxx3024
7.3
14.6
7.3
14.6
7.3
14.6
4.9
9.5
E84Dxxxx4024
9.5
19.0
9.5
19.0
9.5
17.0
6.3
9.5
E84DHxxx7524
16.0
32.0
16.0
32.0
16.0
30.0
10.7
21.3
I
aNx
Rated value of continuous output current
I
aMx
Maximum output current (overload current)
Periodic load change of 3 s with I
aMx
and recovery time of 12 s according to
the tables under chapter
Can be obtained in the setting "x kHz fixed/..." in C00018
Switching
frequency
If the maximum heatsink temperature is reached, the switching frequency is
reduced to 4 kHz.
In the setting "x kHz var./..." in C00018 the switching frequency is reduced
depending on the output current.
Depending on the switching frequency and e.g. the ambient temperature, it
may be required to reduce the output current (chapter 4.1, operating
conditions).
Summary of Contents for 8400 protec
Page 2: ...0Fig 0Tab 0...
Page 190: ...Appendix Declarations and certificates 13 190 EDS84DPS424 EN 5 0...
Page 191: ...Appendix Declarations and certificates 13 191 EDS84DPS424 EN 5 0...
Page 192: ...Appendix Declarations and certificates 13 192 EDS84DPS424 EN 5 0...
Page 193: ...Appendix Declarations and certificates 13 193 EDS84DPS424 EN 5 0...
Page 194: ...Appendix Declarations and certificates 13 194 EDS84DPS424 EN 5 0...