Technical data
Overcurrent operation
56
EDS84DPS424 EN 5.0
4.4
Overcurrent operation
The controllers are designed for an overcurrent limited in time. The load due to defined,
cyclic operation is determined by the "Ixt" monitoring function. The "Ixt" function
comprises two moving averaging procedures which are checked in parallel:
ƒ
temporary moving averaging of the apparent motor current for pulse loads
ƒ
continuous moving averaging of the apparent motor current for permanent loads
Type of utilisation
Utilisation cycle
Monitoring function
Condition
Code
Pulse utilisation
15 s
I
aNx
> 160 %
Display in C00064/2
Display of the maximum
value in C00064/1
Permanent utilisation
180 s
The monitoring function is
permanently active.
Display in C00064/3
Display of the maximum
value in C00064/1
If the maximum value in code C00064/1 exceeds 100%, a "warning" will be generated or
a "trip" will be triggered (according to setting).