Diagnostics
Display of operating data, diagnostics
Extensions in EMS version
161
EDS84DPS424 EN 5.0
10.1.2
Extensions in EMS version
Pos.
Colour
Status
Description
BUS−RDY
green
blinking
Communication has been established
on
Communication has been stopped
off
Communication is not initialised
BUS−ERR
red
blinking fast
Communication error
For PROFINET: Node not recognised
blinking
For PROFINET: Node recognition
on
Communication error
LED1
yellow
−
Signalling controlled by the PLC program with adjustable
blinking speed
LED2
LED3
(PLC−RDY)
green
flashes
PLC program is not available
blinking fast
PLC program is loaded/saved or parameters are saved
blinking
PLC program is started
on
PLC program is stopped
off
PLC status is undefined / device is switched off
PLC−ERR
red
flashes 3x
Internal system error
flashes 2x
Parameter version or checksum invalid
flashes
Retain memory error
blinking fast
PLC program is stopped by watchdog monitoring
blinking
Error
off
No error / device switched off
Half wave
Half wave coded
DECA
LED4
(PLC−Com)
yellow
flashes 3x
Control bar: full
wave
−
−
flashes 2x
Control bar:
negative half
wave
−
Pre operational
flashes
Control bar:
positive half wave
−
Silent mode
blinking fast
−
Command received
Operational
blinking
Error
Error
Error
on
−
−
Warning
off
Control bar: no half wave
Not activated
Summary of Contents for 8400 protec
Page 2: ...0Fig 0Tab 0...
Page 190: ...Appendix Declarations and certificates 13 190 EDS84DPS424 EN 5 0...
Page 191: ...Appendix Declarations and certificates 13 191 EDS84DPS424 EN 5 0...
Page 192: ...Appendix Declarations and certificates 13 192 EDS84DPS424 EN 5 0...
Page 193: ...Appendix Declarations and certificates 13 193 EDS84DPS424 EN 5 0...
Page 194: ...Appendix Declarations and certificates 13 194 EDS84DPS424 EN 5 0...