Electrical installation − EMS version
Devices in a power range of 0.75 ... 4 kW (3/PE AC 400 V)
Terminal assignment of the power connections
125
EDS84DPS424 EN 5.0
X21 − motor connection
− device version E84Dx
H
...
Pin
Connection
Description
Data
Type Han 10E, sockets
84DWTX0212
1
U
Motor phase U
Max. 4 mm
2
Max. output voltage: mains voltage
Max. permanent output current:
type−dependent
2
V
Motor phase W
3
W
Motor phase V
4
BD1
Motor holding brake
Max. 4 mm
2
9
BD2
Motor holding brake (reference
conductor)
5
+PTC
Motor temperature monitoring
Max. 4 mm
2
PTC thermistor (PTC) or thermal
contact (NC contact)
10
−PTC
6, 7, 8
n. c.
−
−
PE
PE conductor
Max. 4 mm
2
, above housing
Stop!
Damage of the devices
A defective motor holding brake or a short circuit on the X21 connection
(motor and built−on accessories) causes internal damage to the device.
Possible consequences:
ƒ
If a defective motor holding brake is connected, the replacement device is
also damaged immediately.
Protective measures:
ƒ
When devices are replaced due to malfunction of the brake control, ensure
that defect−free motor holding brakes are connected.
ƒ
Check whether the motor holding brake and the connecting cable are free
from defects.
ƒ
Replace or repair defective components.
Note!
In the Lenze setting, the temperature monitoring of the motor is activated! To
start motors without thermal detectors, the response of the motor
temperature monitoring must be deactivated (C00585). Alternatively, a wire
jumper bPTC and −PTC can be used to simulate a normal
temperature.
Summary of Contents for 8400 protec
Page 2: ...0Fig 0Tab 0...
Page 190: ...Appendix Declarations and certificates 13 190 EDS84DPS424 EN 5 0...
Page 191: ...Appendix Declarations and certificates 13 191 EDS84DPS424 EN 5 0...
Page 192: ...Appendix Declarations and certificates 13 192 EDS84DPS424 EN 5 0...
Page 193: ...Appendix Declarations and certificates 13 193 EDS84DPS424 EN 5 0...
Page 194: ...Appendix Declarations and certificates 13 194 EDS84DPS424 EN 5 0...