Technical data
General data and operating conditions
44
EDS84DPS424 EN 5.0
Open and closed loop control
Open and closed loop control processes
VFCplus:
V loop (linear or square−law)
V/f closed loop
SLVC:
Sensorless vector control (torque/speed)
Only for HighLine
device version
SC:
Servo control (torque/speed)
from SW version 12
VFCplus eco:
Energy−efficient V/f characteristic
SL PSM:
Sensorless synchronous control (torque/speed)
Switching frequency
2 kHz, 4 kHz, 8 kHz, 16 kHz,
Optionally noise optimised or power−loss optimised
Torque behaviour
Setting range
1 : 10
In a setting range of 3 ... 50 Hz
Sensorless vector control (speed)
Minimum output
frequency
0.5 Hz (0 ... M
rated
)
Setting range
1 : 10
Based on 50 Hz and M
rated
Accuracy
0.5 %
In a setting range of 3 ... 50 Hz
Smooth running
0.1 Hz
Output frequency
Range
−1000 Hz ... +1000 Hz
Absolute resolution
0.2 Hz
Standardised
resolution
Parameter data: 0.01 %, process data: 0.006 % (= 2
14
)
Digital setpoint selection
Accuracy
0.01 %
Analog setpoint selection
Accuracy
%
Based on the final value